Parameter Parameter text Parameter Value Unit
Note: To change P0595 you first need to set P0010 = 5, and then set P0010 back to 0 afterwards.
p595 Selecting technological units [5] Pa
p596 Reference quantity, technological units 100
p753[0]
CU analog inputs smoothing time constant, AI0
(T. 3/4)
500 ms
Note: The Ramp-up, Ramp-down, and Minimum Speed parameters are shown for the tuning process of the actual stair-press system, and may
have to be adjusted to suit.
p1080[0] Minimum speed 450 rpm
p1120[0] Ramp-function generator ramp-up time 30 s
p1121[0] Ramp-function generator ramp-down time 30 s
p1210 Automatic restart, mode
[26] Acknowledging all faults and reclosing for an ON
command
p2200[0] BI: Technology controller enable Control_Unit : r722.0
p2201[0] CO: Technology controller, fixed value 1 40 Pa
p2253[0] CI: Technology controller setpoint 1 Control_Unit : p2201
p2264[0] CI: Technology controller actual value Control_Unit : r755[0]
p2267 Technology controller upper limit actual value 120 Pa
p2268 Technology controller lower limit actual value -10 Pa
Note: The Prop gain and Integral time parameters are shown for the tuning process of the actual stair-press system, and may have to be adjusted
to suit.
p2280 Technology controller proportional gain 1.2
p2285 Technology controller integral time 25 s
Note: Set the PID Loop minimum output value to match the minimum motor speed (P1080). For example; 30% for 15Hz (when the max speed is
50Hz).
p2292 CO: Technology controller minimum limiting 30 %
p2302 Technology controller output signal starting value 35 %
p3880 BI: ESM activation Control_Unit : r722.0
p3881 ESM setp source [4] Setpoint from technology controller
p3884 CI: ESM setpoint technology controller Control_Unit : p2201
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r755[0]
CU analog inputs actual value in percent, AI0 (T.
3/4)
71.34 %
r2260
CO: Technology controller setpoint after ramp-
function generator
40 Pa
r2272 CO: Technology controller actual value scaled 71.34 Pa
r2273 CO: Technology controller error -31.34 Pa
r2294 CO: Technology controller output signal 0 %