Connecting the Network
3-13
SIMATIC 505 PROFIBUS-FMS CP User Manual
5. Remove
0.25 inches (6 mm) of insulation at the wire ends.
6.
Insert the signal wires into the cable terminals.
Be sure to connect the same wire color to the TX/RX+ pin for every
device throughout your system. Crossing the wires at any point creates
communications problems.
7.
Set the termination switch to the correct position. See Figure 3-10.
Switch
position ON
(termination and
bias enabled).
ABAB
ON
OFF
Switch position OFF
(termination and
bias disabled).
ABAB
ON
OFF
A.
Attaching connector at segment end
B. Attaching connector to midpoint of segment
Figure 3-10 Attaching
Connector and Selecting T
ermination
8.
Put the cover back on the connector housing.
Be sure that the bare cable shielding makes contact with the metal
cable guide on the connector
, to ensure proper grounding for the
connection.
9. T
ighten the connector housing screws to a maximum torque of 8 in-lb
(0.9 N-m) in order to ensure a good connection.