17/18
Building Technologies Central communication unit OZW775 V3.0 CE1N5663en
HVAC Products 29.06.2009
Connection diagrams
D2
M
D3 D4
MD5
D6 D8MMD1
G
5662G02
D7
Q21
Q22 Q31
Q32G0
X1 M
X2
X3 M X4 X5 M X6 X7 M X8 CE- CE+
Q73
Q74
Q83 Q84
Q11
Q12
Q41 Q42
Ethernet
RJ45Modem
D1…D8 Digital inputs
X1…X8 Universal inputs
M Ground for digital inputs, measuring ground for universal inputs
CE- KNX bus connection (negative)
CE+ KNX bus connection (positive)
G, G0 Operating voltage AC 24 V
Q… Relay outputs
G
G
G0
G0
K1
5663A02
AC 24 V
Q21
CE-X2M
F2
F1
B1
Ethernet
X3.......X8X1D3.......D8D2MD1
Q22
Q31
Q32
Q73
Q74
Q83
Q84
B2 N2
N3
KNX
0...10 V
Q11
Q12
Q41
Q42
Ethernet
RS-232
RJ45CE+Modem
N1
N N
L
K2
K3
L
N1 Central communication unit OZW775
N2, N3 Synco device in KNX network
F1, F2 Device with potential-free contact output
B1 Sensor with passive signal
B2 Transmitter with active signal
K1, K2 Contactor (control by relay with NC contact)
K3 Contactor (control by relay with NO contact)
RJ45 plug (screened), standard assignment as per AT&T256.
1 Tx + 5 Not used
2 Tx – 6 Rx –
3 Rx + 7
Not used
1
3206Z01
2345678
5663Z21
4 Not used 8
Not used
Modem connection (D-pins, 9-pin), interface definition as per RS-232.
1 DCD Data carrier detect 6 DSR Data set ready
2 RXD Received data 7 RTS Request to send
3 TXD Transmit data 8 CTS Clear to send
4 DTR Data terminal ready 9 NC Not connected
5663Z22
6789
1
23
45
5 GND Signal ground
Connection diagram
Connection diagram
Pin assignment
Ethernet card OZZ7E5
Modem connection,
central communication
unit