LED displays
Run (green) Dark No operating voltage AC 24 V or unit is starting.
Lit Unit ready to operate.
Flashing Communicating with ACS.
Dark No fault (normal operating state).
Local (red)
Lit Central communication unit faults and/or signal at fault inputs "Hours run for
service reached".
Flashing Fault unacknowledged.
Without configured fault relay "System" in the OZW775:
System (red)
Dark No fault (normal operating state).
Lit Device fault in KNX network.
With configured fault relay "System" in the OZW775:
Dark No fault (normal operating state).
Lit Device fault in KNX network, fault relay acknowledged.
Flashing Device fault in KNX network, fault relay unacknowledged.
Dark No CF card integrated.
CF cards (green)
Lit CF card integrated.
Flashing CF card is being integrated or removed
(after pressing button "long" on "Config").
Dark No bus power supply.
KNX (green/red)
Steady green Bus power supply available.
Flashing green Data exchange via KNX.
Steady red Unit in addressing mode.
Operating buttons
Pressing the button briefly ("short") means <2 seconds, "long" >4 seconds.
Config Short No function.
Long Integrate or remove CF card (or both CF cards).
Short Acknowledge "Local" fault, fault relay "System".
ck
Long See “Button combinations“.
Short No function.
Report
Long See “Button combinations“.
Short Initializes modem, checks modem connection. Modem
Long Initializes modem, sends system report to configured receivers.
Button combinations For button combinations, always press "long" (>4 seconds).
Simultaneously press "Modem" and "Report" (programming mode).
ddressing mode
Simultaneously press "Modem" and "Ack".
Restart central unit
Simultaneously press "Modem", "Ack", and "Config".
Default state
Note: All configuration data and settings are reset. The device list and all unsent
messages are deleted. History data is not deleted.
12/18
Building Technologies Central communication unit OZW775 V3.0 CE1N5663en
HVAC Products 29.06.2009