AC Power (Mains) Connections, Continued
Instructions,
continued
Step Action
7. Route input power, in accordance with pertinent electrical
codes and regulations, to ANG_EN.
To make the connections easier we have provided J1 as a removable
connector. Simply grasp the top portion of the connector and pull it
straight out from the base connector.
Installation Note
8. Locate the AC Power Input connector. To make the AC
connections easier the Power Input Connector comes
apart. Simply loosen the two recessed captive screws,
grasp the top portion of the connector and pull it straight
out from the base connector.
Loosen the top wire retaining screws from the removed
connector. Strip the insulation ¼ -inch back from each of
the input power leads. Insert each lead in
9. Plug the connector back into its base and secure down with
the two recessed captive screws.
10.
Locate the ANG_EN chassis ground lug
and connect
wire from it to the building’s ground connection.
11. Inspect all connections for shorts or loose connections.
12. You are now ready to connect the Data Hiway cable;
continue with Data Hiway Connections, page
20.
2000590-001 Installation 19