Command Interface
5-19
SIMATIC NET CP 243-2 AS-i Master
C79000-G8976-C142/02
5.2.7 Get_Extended_Permanent_Configuration
Purpose
This call reads the following configuration data (configured data) of an addressed
AS-i slave stored on the EEPROM of the AS-i master.
I/O configuration
ID code
Extended ID1 code
Extended ID2 code
The configuration data are specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the Job Data in the Send Buffer
Bank Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
2 0 Command number 26
H
2 1 Slave address
Structure of the Job Data in the Receive Buffer
Bank Byte Meaning
Bit 7 Bit 4 Bit 3 Bit 0
2 0 Echo of the command number: 26
H
2 1 Command status
2 2 ID code I/O configuration
2 3 Extended ID1 code Extended ID2 code