CP 523 Hardware Installation
3.2.3 Pin Assignments of Backplane Connector X1
M +5 V
UBATT PESP
ADB 0 RESET
ADB 1 MEMR
ADB 2 MEMW
ADB 3 RDY
ADB 4 DB 0
ADB 5 DB 1
ADB 6 DB 2
ADB 7 DB 3
BAU ADB 8 DB 4
ADB 9 DB 5
ADB 10 DB 6
ADB 11 DB 7
BASP
M
d b z
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Figure 3-5. Pin Assignments of Backplane Connector X1
3.3 Cable Length
The cable lengths given below are contingent to error-free data transmission.
TTY interface
CP 523 active TTY : maximum cable length 10 m/33 ft.
Peripheral device active TTY : Refer to the User's Guide for the relevant device for the
permissible cable length (maximum 1000 m/3280 ft).
Note:
Voltage drops on the cable and the module's sending and receiving elements must be noted
when using longer cables ( 2.2).
RS-232-C (V.24) interface
Cable length is not critical up to 15 m/49 ft. In general, longer cables can be used in conjuction
with lower baud rates.