CP 523 Using the ”SEND” and ”Receive” Function Blocks
8.1.2 Setting ”SEND” FB 200 Parameters
If you want to send a message frame of specific size, specify the length of the message frame to be
sent (in words) in the QLAE parameter. The "ENDZ" parameter is not significant here. In 3964(R)
mode, the message frame size must be specified.
If you want to send a message frame with end-of-text characters (variable length), specify "zero"
in the QLAE parameter and two end-of-text characters in the "ENDZ" parameter. Both end-of-text
characters must be in the same data word.
Example: End-of-text character 0D 0D
H
valid: DW n KH: 44 44 invalid: DW n KH: 44 0D
DW n+1 KH: 0D 0D DW n+1 KH: 0D 00
Table 8-2. Setting the "ENDZ" and "QLAE" Parameters
ENDZ
(End-of-text char.)
QLAE
(Frame length)
Transmission mode
=0
>< 0
=0
>< 0
>< 0
>< 0
=0
=0
Message frame of specific length
Message frame of specific length
NOT PERMISSIBLE
Message frame with end-of-text characters
EWA 4NEB 811 6044-02a
8-3
Vista de página 192