Engineer programming via the browser
Configuring zones, doors and areas
168
Siemens AB
A6V10276959
Security Products
18.11.2011
15.8.2.1 Entry/Exit
Configure the following Entry/Exit settings:
Entry time
The time (in seconds) allowed for unsetting to be completed. The entry
time applies to all entry/exit zones in that area (default: 45 seconds)
See Timers [➙ 160].
Exit time
The time (in seconds) allowed for a user to leave a protected area
before setting is complete. The exit time applies to all entry/exit zones in
that area (default: 45 seconds) See Timers [ 160].
Disable Exit Time
Select if no exit timer is required and setting is activated by ‘Exit term’
zone or ‘Entry exit’ zone with ‘Final exit’ attribute. See Timers [➙ 160].
Fob Unset Entry
FOB will only unset when entry timer is running. Default is enabled.
15.8.2.2 Partset Options
Configure the operation of particular zones for both Partset A and Partset B modes
as detailed below:
Partset Enable
Enable PartSet for A and B operation as required.
Partset Timed:
Tick the relevant checkbox (Partset A or B) to apply the exit
timer to the Partset A or B mode.
Partset Access:
Tick the relevant checkbox to change access zones into
entry/exit type zones for either Partset A or B operation. This
feature is useful for a domestic installation where a Passive
Infrared (PIR) sensor is located in the hallway. If the user
partsets the system at night and returns downstairs during the
night, he/she may unintentionally activate the PIR sensor in
the hallway and trigger the alarm. By setting the partset
Vista de página 167