SIMATIC IFP1900 MT
16 A5E31990455-AA, 04/2013
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the device.
Ambient conditions Permitted range Comments
Temperature:
Vertical mounting
Mounting at an angle
From 0 to 45 °C (horizontal)
From 0 to 40 °C (vertical)
From 0 to 40 °C (horizontal)
From 0 to 35 °C (vertical)
Slope angle max. 35°
Relative humidity 10 to 90%, without condensation
Atmospheric pressure 1 080 to 795 hPa Corresponds to an elevation of -1000 m
to 2000 m
SO
2
: < 0.5 vpm;
Relative humidity <60%, no condensation
Test: 10 cm
3
/m
3
; 10 days Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity <60%, no condensation
Test: 1 cm
3
/m
3
; 10 days
Information on insulation tests, protection class and degree of protection
Test voltages
Insulation strength is demonstrated in the type test with the following test voltages in accordance with IEC 61131-2:
Circuits with a nominal voltage of U
e
to other circuits or
ground
Test voltage
24 V 707 V DC or 500 V AC
Protection class
Protection class I in accordance with IEC 61140, i.e. a protective conductor connection to the device is required. You can
find information on connecting the productive conductor at: IFP1500, IFP1900, IFP2200 operating instructions
(http://support.automation.siemens.com/WW/view/en/65288650
).
Protection against foreign objects and water
Degree of protection in accordance with
IEC 60529
Explanation
Front When mounted:
● IP65
● Front face only Type 4X/Type 12 (indoor use only)
Rear panel IP20
Protection against touching with back of hand.
There is no protection against ingress by water.
The degree of protection of the device front can only be guaranteed if the mounting seal lies flush against the mounting
cutout.