Siemens RDU340… Basic Documentation CE1P3078en
Building Technologies Functions 2014-09-05
# Parameter
Factory
setting
Setting range
RDU340
Service Level
P01 Control sequence
(for application "single duct" only)
1 (Cooling only) 0:= Heating only
1:= Cooling only
2:= Manual H/C
3:= Auto changeover
P02 Mode selection via user operating mode button 1 (Stb, Comf) 1 = Stb,Comf
2 = Stb, Comf, Eco
P04 Selection of °C or °F °C (0) °C
(1) °F
P05 Sensor calibration 0.0 K – 3 ... +3 K
P06 Standard temperature display 0 (Room temp) 0:= Room temperature
1:= Setpoint
P07 Additional user info 0 (no display) 0:= no display
1:= Temp in °C and °F
P08 Comfort basic setpoint 21 °C 5 ... 40 °C
P09 Minimum setpoint limitation for Comfort (WminComf) 5 °C 5 ... 40 °C
P10 Maximum setpoint limitation for Comfort (WmaxComf) 35 °C 5 ... 40 °C
P11 Heating setpoint for Energy Saving (WheatEco) 15 °C OFF, 5 °C…WcoolEco
P12 Cooling setpoint for Energy Saving (WcoolEco) 30 °C OFF, WheatEco…40 °C
P14 Keypad lock
(Press the operating mode button
for 7 seconds to enable
or disable the keypad lock)
0 (Unlocked) 0:= Unlocked
1:= Auto lock
2:= Manual lock
P01 is not available when the controller is commissioned as single duct with el.
heater (DIP switch #1 = ON)
P02 is not available when the controller is commissioned for manual
heating/cooling changeover (P01=2)
Parameter display depends on selected application and function
(x) Not available
Control parameters
Note