s Room thermostat with KNX communications RDG400KN Basic Documentation Edition: 1.0 CE1P3192en 20 Jul 2010 Building Technologies
10 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Summary 20 Jul 2010 Synco 700 Building automation and con
11 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Summary 20 Jul 2010 2.5 Equipment combinations Type of unit Pro
12 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Summary 20 Jul 2010 Electromotoric ON/OFF valve and actuator
13 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3. Functions 3.1 Temperature control Sett
14 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.2 Operating modes The thermostat&apos
15 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.2.1 Different ways to influence the ope
16 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 If a time schedule via bus is present, e
17 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Comfort mode can be temporarily extended (
18 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Function if no time schedule is received
19 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.2.2 Communication examples The followi
2 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Contents 20 Jul 2010 Contents 1. About this document ...
20 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Interaction of user operation (operating
21 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.3 Room temperature setpoints 3.3.1 Des
22 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 If a setpoint (Economy or Protection) is
23 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 1) Only required for heating AND cooling
24 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.4 Applications overview The thermosta
25 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.5 Additional functions The supply air
26 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 The QAH11.1 cable temperature sensor for
27 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Dew point monitoring is essential to preve
28 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6 Control sequences 3.6.1 Sequences o
29 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.2 Application mode The behavior of t
3/78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Contents 20 Jul 2010 3.10.3 Zone addressing in LTE mode (in conjun
30 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 The state (heating or cooling) of the th
31 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.3 Minimum and maximum air volume The
32 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.4 Single-duct On single-duct appli
33 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.5 Single-duct with electric heater G
34 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Sequences ON/OFF electrical heater Mod
35 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.6 Single duct with radiator or floor
36 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Without a valid bus signal for changeove
37 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.7 Single-duct with heating / cooling
38 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Without a valid bus signal for changeove
39 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.6.8 Setpoints and sequences Comfor
4 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies About this document 20 Jul 2010 1. About this document 1.1 Revi
40 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.7 Control outputs 3.7.1 Overview Di
41 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.7.3 Control output for electrical heate
42 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Output Y1 provides the OPEN command, and
43 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.7.4 Control outputs configuration (sett
44 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.8 Multifunctional input, digital inpu
45 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 # Function of input Description Type
46 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.9 Handling faults When the room temp
47 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 RDGSensorOutside temperature zone 1Air dis
48 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 The device will send and receive LTE com
49 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Air distribution zone Zone = ---, 1...3
5 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies About this document 20 Jul 2010 1.3 Before you start 1.3.1 Copy
50 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.10.5 Send heartbeat and receive timeo
51 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.10.9 Electric heater interlock by suppl
52 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.10.11 Fault function on KNX If a faul
53 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.10.12 Emergency control (LTE Mode only)
54 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.11 Communication objects (S-mode) 3.11
55 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.11.2 Description of communication objec
56 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Obj Object name Function Type/ length
57 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.12 Control parameters A number of contr
58 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.12.2 Parameter setting / download via
59 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.12.3 Parameters of the "Service le
6 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies About this document 20 Jul 2010 1.4 Target audience, prerequis
60 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 3.12.4 Parameters of the "Expert l
61 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Functions 20 Jul 2010 Parameter Name Factory setting Range
62 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 4. Handling 4.1 Mounting and installatio
63 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 After power is applied, the thermostat rese
64 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 Recalibrate the temperature sensor if
65 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 4.3 Operation See also Operating Instruct
66 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 # Symbol Description # Symbol Descr
67 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Handling 20 Jul 2010 4.4 Remote operation The RDU thermostats c
68 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Supported KNX tools 20 Jul 2010 5. Supported KNX tools 5.1 ET
69 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Supported KNX tools 20 Jul 2010 5.2.1 Parameter settings in ACS
7 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Summary 20 Jul 2010 2. Summary 2.1 Types Product no. Stock numbe
70 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Supported KNX tools 20 Jul 2010 5.2.2 Operation and monitorin
71 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Supported KNX tools 20 Jul 2010 ACS Operating offers plant diagr
72 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Supported KNX tools 20 Jul 2010 5.2.3 Operation and monitorin
73 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Connection 20 Jul 2010 6. Connection 6.1 Connection terminals
74 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Mechanical design 20 Jul 2010 7. Mechanical design 7.1 General
75 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Technical data 20 Jul 2010 8. Technical data Operating voltage
76 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Technical data 20 Jul 2010 Setpoints Current temperature value
77 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Index 20 Jul 2010 Index 3 3-position control signal...
78 / 78 Siemens RDG400KN Basic documentation CE1P3192en Building Technologies Index 20 Jul 2010 V VAV changeover ...