If the keypad lock function is enabled by parameter P14, then the keypad will be
locked or unlocked by pressing 7 seconds (RDF600...: 3 seconds) on the operating
mode button
.
If “Auto lock” is configured, then the controller will automatically lock the keypad 30
seconds after the last adjustment.
4.6 Control sequences
The controller can be used in systems featuring:
Heating or cooling mode (P01=0 or P01=1)
Manual heating/cooling changeover (P01=2)
Automatic heating/cooling changeover (P01=3)
Heating and cooling mode (e.g. 4-pipe system) (P01=4)
The relevant modes are available and can be adjusted via commissioning
parameter “Control sequence” P01, depending on the selected application.
Sequence
T °C
T °C
T °C
T
T °C
Parameter P01 = 0 P01 = 1 P01 = 2 P01 = 3 P01 = 4
Mode
Available for:
Heating mode
Cooling mode
*) 2-pipe with
el. heater
Manually select
heating or
cooling mode
Automatic
heating/cooling
changeover via
external water
temperature
sensor or
remote switch
Heating and
cooling mode,
i.e. 4-pipe
2-pipe,
2-pipe & el. heater
4-pipe