Página 1 - Position Decoder Module

SIMATIC S5IP 240Counter/Positioning/Position Decoder ModuleManual EWA 4NEB 811 6120-02bEdition 03

Página 2 - First Printing, March 1991

IP 240 IntroductionConventionsThe following conventions are used in this book and are listed for your reference:Convention Definition ExampleA box t

Página 3 - EWA 4NEB 811 6120-02c

Position Decoding IP 240DB20 LEN=35

Página 4

IP 240 Position DecodingStart routine FB 20Reset the flagareas usedConfigureIP 240 channel 1for positiondecodingSet output”RET INTPNT”EndEWA 4NEB 81

Página 5 - IP 240 Preface

Position Decoding IP 240Cyclic program FB 21yesnoyesyesyesyesnonoFB 26FB 25FB 24FB 23FB 22yesnoQ ”RET INTPNT”set?Enable set andstart buttonpressed?I

Página 6 - Introduction

IP 240 Position DecodingOperation/traverse program FB 25 yesnoyesyesFB 25nonoyesBackward traverse programactive?noForward traverseprogram active?Ent

Página 7 - Introduction IP 240

Position Decoding IP 240Control and output program FB 26noyesnoFB 26yesnoEMERG STOP”pressed?yesnoError bitset? (FY 11)yesnoLimit switch pressed?Rese

Página 8

IP 240 Position DecodingInterrupt service routine FB 27 and FB 28noyesnononoyesFB 27noRead interrupt req.(FB 170 FCT 3)Interrupt fromchannel 1?Inter

Página 9

Position Decoding IP 240OB 1 LEN=8 NETWORK 1 0000

Página 10 - Conventions

IP 240 Position DecodingFB 20 LEN=52

Página 11 - EWA 4NEB 811 6120-02a

Position Decoding IP 240FB 21 LEN=33

Página 12

IP 240 Position DecodingFB 22 LEN=34NETWORK 1 0000 REDEFINE INITIAL POINTFB22 : R

Página 13 - 1 System Overview

2 Module Description and Accessories3 Addressing4 Hardware Installation5 Operation6 Functional Description7 Position Decoding8 Counting9 IP 252 Expans

Página 14 - System Overview

Position Decoding IP 240FB 23 LEN=75

Página 15

IP 240 Position DecodingFB 23 LEN=75

Página 16

Position Decoding IP 240FB 24 LEN=97

Página 17

IP 240 Position DecodingFB 24 LEN=97

Página 18 - 2.2 Technical Specifications

Position Decoding IP 240FB 25 LEN=67

Página 19 - 2.2.2 Counting

IP 240 Position DecodingFB 25 LEN=67

Página 20 - 2.2.3 Inputs/Outputs

Position Decoding IP 240FB 26 LEN=75

Página 21

IP 240 Position DecodingFB 26 LEN=75

Página 22

Position Decoding IP 240FB 27 LEN=26NETWORK 1 0000 INTERRUPT SERVICE ROUTINE FOR

Página 23 - 2.3 LEDs

IP 240 Position DecodingFB 28 LEN=81NETWORK 1 0000 INTERRUPT SERVICE ROUTINE FOR

Página 24 - 2.4 Order Numbers

Figures1-1. Modes of the IP 240 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 11-2. IP 240 with and with

Página 25

Position Decoding IP 240FB 28 LEN=810039 REF8 :003A :AN F 16.7

Página 26

IP 240 Position DecodingFB 38 LEN=39NETWORK 1 0000 SAVE FLAGSFB38 SAVES FLAG WOR

Página 27 - 3 Addressing

Position Decoding IP 240FB 39 LEN=37NETWORK 1 0000 LOAD FLAGSWRITE THE STATES OF

Página 28 - Addressing IP 240

IP 240 Position DecodingFB 169 LEN=47NETWORK 1 0000NAME :STRU.WEGID :BGAD I/Q/D/B/T

Página 29 - IP 240 Addressing

8 Counting8.1 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8- 18.2 Principle of Operat

Página 30

Figures8-1. Actual Value Range and Overrange in Counting Mode . . . . . . . . . . . . . . . . . 8 - 18-2. Sequence Diagram for Counting Mode . . . .

Página 31

IP 240 Counting8 Counting8.1 ApplicationsIn this mode, the IP 240 can be universally used for pulse counting. The module can process pulsetrains wit

Página 32 - 4 Hardware Installation

Counting IP 240When the defined actual value range is exceeded, the counter enters overrange and the IP setsstatus bit UEBL (overflow).When set, the

Página 33

IP 240 Counting8.2.2 Final ValueStoring the final countWhen you evaluate the actual value, you are evaluating the current count. The IP also makes t

Página 34

Counting IP 240The following options are available for forcing the output:a) The digital output is to be set when the actual value reaches ”0”, and

Página 35 - 4.2.1 Wiring Method

IP 240 System Overview1 System OverviewIntelligent input/output modules (I/Os) extend the field of applications of the SIMATIC S5programmable contro

Página 36

IP 240 Counting8.2.4 Flagging with Status BitsStatus data is updated in every cycle of the module firmware on the IP.If you want information about t

Página 37

Counting IP 2408.2.5 Interrupt Generation and ProcessingStatus bits REF1, REF2, UEBL and UEBS can trigger an interrupt and are stored in the interru

Página 38 - 4.3.1 Inputs

IP 240 Counting8.3 Initializing Standard Function Blocks and Data Block Contents8.3.1 Configuring Function BlockFB 171 (STRU.DOS) Configuring and p

Página 39

Counting IP 240Table 8-1. Parameters for Configuring FB 171Para- Name meter Data Description typeBGAD D KF Module starting addressKANR D KF Cha

Página 40

IP 240 CountingEXT : KH 0000 to 0001 Control of count enabling by external or internal starting signalBit 0=1 Control of start of count by active si

Página 41

Counting IP 240Technical SpecificationsBlock number : 171Block name : STRU. DOSPLC Library numberCall length/Block lengthCPU Processing time 1S5-115

Página 42

IP 240 Counting8.3.2 Control Function BlockFB 172 (STEU.DOS) Control function block for counting. Functional descriptionThe control function block

Página 43 - ((1887/3))

Counting IP 240NoteIn the standard function blocks, scratch flags and system data areas are used fordata interchange with the IP 240 ( Technical Sp

Página 44

IP 240 Counting8.3.3 Contents of the Data BlockThe data block to be created must have least 36 words (DW0 to DW 35). The number of theselected data

Página 45

Counting IP 240Control bitsDL 17DR 177Databyte6 5 4 3 2 1 0000STRT0000DA1F0DA1S0AMSK000BitAMSK =1 All process interrupts for the channel are masked,

Página 46

System Overview1P 240In the position decoding, counting and positioning modes, the 1P 240 can be used as a standalonemodule in the U-range programmabl

Página 47

IP 240 CountingInterrupt request bytes for channel 1 and channel 2Channel 1Channel 1Channel 2Channel 2DL 20DR 20DL 21DR 217Databyte6 5 4 3 2 1 00000

Página 48

Counting IP 240Actual valueThe specified value is an absolute value. The sign (SG) is indicated in the status area (DW 19).Actual value in BCD000000

Página 49

IP 240 Counting8.4 Example for Counting: Fast Filling with Loose MaterialThe throughput in filling with loose material is measured using a pulse enc

Página 50

Counting IP 240Inputs, outputs, flags, timers and counters usedOPERAND SYMBOL COMMENTI 5.2 EMERG STOPI 5.3 START FILL PUSHBUT

Página 51

IP 240 CountingDB14 LEN=43

Página 52

Counting IP 240DB20 LEN=35

Página 53

IP 240 CountingFB 40 initialization programyesyesnonoyesyesnonoyesDepending on cause Q ”FILLING”flashes fast or slowlyReset F ”FILL ACTIV”Reset auxi

Página 54

Counting IP 240OB 1 LEN=8

Página 55

IP 240 CountingFB 38 LAE=39

Página 56 - 6.1.4 LEDs

Counting IP 240FB 39 LEN=37

Página 57 - 6.2 Programming

3 Addressing4 Hardware Installation5 Operation6 Functional Description7 Position Decoding8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Inte

Página 58 - 6.2.3 Data Blocks

IP 240 CountingFB 40 LEN=31

Página 59 - 6.4 Fault and Error Flagging

Counting IP 240FB 41 LEN=111

Página 60

IP 240 CountingFB 41 LEN=111

Página 61

Counting IP 240FB 171 LEN=38

Página 62 - 6.5 Multiprocessor Operation

10 Positioning11 Direct Data Interchange with the IP 24012 Response Times13 Encoder Signals14 Error Messages9 IP 252 Expansion9.1 Speed Measurement wi

Página 63

TablesFigures9-1. Speed Measurement with the IP 252 Closed-Loop Control Module . . . . . . . 9 - 19-2. Actual Speed Measurement via the IP 240 Modul

Página 64

IP 240 IP 252 Expansion9 IP 252 ExpansionWhen the IP 240 is used with the IP 252 closed-loop control module, control lines, which are onlyimplemente

Página 65 - 7 Position Decoding

IP 252 Expansion IP 240By expanding the IP 252 with IP 240 modules, it is possible to provide two or more control loopswith actual values from incre

Página 66

IP 240 IP 252 Expansion9.2 Data Interchange between S5 CPU -- IP 240 -- IP 252 During operation, data traffic between the IP 240 and the IP 252 is c

Página 67 - 7.2.2 Resolution

1P 252 Expansion1P 2409.3Configuring—When configuring the 1P 252 closed-loop control module, YOU must W the configuring switches —for speed measurem

Página 68 - 7.2.3 Reference Tracks

Figures2-1. Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2- 42-2. Block Diag

Página 69

IP 240 IP 252 Expansion9.4 Initializing the Configuring Function Block and Data Block Contents9.4.1 Configuring Function BlockFB 173 (STRU. 252) Co

Página 70

IP 252 Expansion IP 240NoteInterrupt servicing is not disabled in the configuring FBs. You must therefore writeyour STEP 5 program in such a way tha

Página 71

IP 240 IP 252 Expansion9.4.2 Data Block ContentsThe data block to be created must have at least 25 words (DW 0=to DW 24). The number of theselected

Página 72

10 Positioning10.1 Application and Functional Description . . . . . . . . . . . . . . . . . . . . . . . 10 - 110.1.1 Application . . . . . . . . . . .

Página 73 - 7.2.4 Hysteresis

11 Direct Data Interchange with the IP 24012 Response Times13 Encoder Signals14 Error Messages10.13 Methods of Synchronization . . . . . . . . . . . .

Página 74

10-1. Overview of IP 240 Configuring and Synchronization Options . . . . . . . . . . 10- 110-2. Controlled Positioning with Two Speeds . . . . . . . .

Página 75

10-1. Switching IP Digital Outputs D1 and D2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10- 310-2. Selecting Positions 0 - 254 . . . .

Página 76

IP 240 Positioning10 Positioning10.1 Application and Functional Description10.1.1 ApplicationIn this mode, the IP 240 enables controlled positioning

Página 77 - 7.2.5 Forcing the IP Outputs

Positioning IP 24010.1.2 Functional DescriptionThis section includes a brief description of the IP 240's method of operation in ”positioning”mo

Página 78

IP 240 PositioningFig. 10-3. Controlled Positioning with the IP 240StartingpositionTargetpositionVSwitchingpointCut-offpointPosition value of thet

Página 79

IP 240 Module Description and Accessories2 Module Description and Accessories2.1 General Technical SpecificationsTemperatureOperation 0 to +55 °C(In

Página 80

Positioning IP 240b) Switching and signalling ranges for a positionDuring the approach to a target position, the IP 240 monitors the entry into rang

Página 81

IP 240 PositioningFig. 10-5. Status Bits on Approach to Position000Approaching the positionin negative directionApproaching the positionin positiv

Página 82

Positioning IP 240b) Approaching the target position in negative directionThe axis is at 1600 increments when the position is selected. The axis mus

Página 83

IP 240 PositioningTable 10-3. Axis Types and Actual Value RangesRotary axis9,999,998Linear axisMaximumactual value Table-9,999,999 +9,999,999-10+1

Página 84

Positioning IP 240b) The IP outputs control the direction of travelThe IP 240 sets one or both outputs in dependence on the required direction of tr

Página 85

IP 240 PositioningTo compensate backlash, you can specify that the IP output is to be disabled on a approach toposition only when the direction of t

Página 86

Positioning IP 240c) Synchronization with an external control signalWhen this method is used, each positive signal edge at the IN input resets the a

Página 87 - 7.3.2 Control Function Block

IP 240 PositioningBCD representationIf you require BCD-coded data for the purpose of documentation, definition or post-processing,you may choose thi

Página 88

Positioning IP 24010.3.2 Data in the Data Block and in the Transfer BufferIf the data interchange with the IP 240• is handled by standard function b

Página 89

IP 240 Positioning• 2-byte-dataTwo bytes are available for the following data items:- Distance value of range BEE3 for position 0Table 10-6. Layout

Página 90

Module Description and Accessories IP 2402.2 Technical SpecificationsThe IP 240 has two independent channels. In the IP 252 expansion mode, the enc

Página 91

Positioning IP 240Numerical representation and ranges for input and output valuesThe table below provides an overview of the digit positions actuall

Página 92

IP 240 Positioning10.4.2 Rotary AxisIn the case of a rotary axis, the traverse path is closed and is not limited. A revolution can comprisea maximum

Página 93

Positioning IP 240Maximum traversing speedThe encoder pulses acquired by the IP are counted in a counter chip. The current (internal) count isread o

Página 94

IP 240 Positioning10.5 Switching the IP OutputsThe IP 240 is equipped with two digital outputs (D1 and D2) for each channel.You have two options for

Página 95

Positioning IP 24010.5.2 The IP Outputs Control the Traversing SpeedWhen you configure DAV=0 or DAV=1, you pass control of the traversing speed to t

Página 96

IP 240 PositioningFig. 10-13. Switching Performance of the IP Outputs when DAV=2OutputD2SampleactualvaluePositionvalidOutputD1BEE1Positive directi

Página 97

Positioning IP 240Fig. 10-14. Contactor Control of a Three-Phase MotorEmer-gencylimitswitchEmer-gencylimitswitchK1 K2 K4K3K1 K2Axis slides Emerge

Página 98

IP 240 Positioning10.6 Backlash Compensation (LOSE) Backlash in the position decoding system reduces the positioning accuracy. To prevent this, allp

Página 99 - 67: KH = 7450;

Positioning IP 240If the actual value is greater than the position value of a newly selected position, the positioningprocedure must be subdivided i

Página 100 - Position Decoding IP 240

IP 240 Positioning10.6.2 Backlash Compensation during Reference Point ApproachCompensation of the backlash during reference point approach ( Sectio

Página 101 - IP 240 Position Decoding

IP 240 Module Description and AccessoriesInput frequencies Pulse inputs:-Symmetrical signals max. 500 kHz in position decoding and positioning modem

Página 102

Positioning IP 240Actual value range and overrangeThe actual value range is defined as -9,999, 999 to +9,999,999.Fig. 10-17. Actual Value Range an

Página 103

IP 240 PositioningYou specify the resolution in configuring parameter AFL:: JU FB 167NAME : STRU.POS::AFL : KF x x=1 Single resolutionx=2 Twofol

Página 104

Positioning IP 24010.7.2 Zero OffsetBy transferring a zero offset (NVER), you can allocate a new actual value to the current position.You may also m

Página 105

IP 240 Positioningb) Additive zero offsetThe new actual value is computed as follows when you specify an additive zero offset: Actualnew=Actualold +

Página 106

Positioning IP 240The table below shows the contents of the data block for a zero offset.A negative value must be spe-cified as two's complemen

Página 107

IP 240 Positioning10.8 Position Data for Positions 1 to 254Position data includes:• the position value designating the absolute location of the posi

Página 108

Positioning IP 240Entering the position numbers and position values in the data blockThe area beginning with DW 60 is reserved for position numbers

Página 109

IP 240 PositioningThe position number assigned to a position need not be identical to the number of the positionentry.It is more practical, however,

Página 110

Positioning IP 240When the actual value is within a range, the associated status bit BEE1, BEE2 or BEE3 is set to zero.Changes in the values of thes

Página 111

IP 240 PositioningTransferring the distance values with the configuring FBThe distance values are initially transferred to the IP 240 when you confi

Página 112

Only qualified personnel should install or maintain this equipment after becoming thoroughly familiarwith all warnings, safety notices, and maintenanc

Página 113

Module Description and Accessories IP 2402.2.3 Inputs/OutputsThe IP 240 provides two options for connecting sensors to the pulse inputs:• All senso

Página 114

Positioning IP 240Zero mark monitoringZero mark monitoring is used to detect spurious or missing pulses, and is possible only when• the number of en

Página 115

IP 240 Positioning10.10 Initializing the Parameters for Interrupt Generation (PRA1, PRA2, ABIT)The following status bits have interrupt capability,

Página 116

Positioning IP 240When using an S5-150U or S5-155U (150 mode), note that the ABIT parameter must also beinitialized. In these programmable controlle

Página 117

IP 240 PositioningTable 10-15. Contents of Data Words 8 to 10DatabyteBit7654 3210DescriptionDL 8 2726252423222120Error no. 3DR 8 2726252423222120E

Página 118

Positioning IP 24010.13 Methods of SynchronizationPositioning is possible with the IP 240 only when the actual value has been synchronized. Threemet

Página 119

IP 240 PositioningFig. 10-22. Location of the Reference Point on Reference Point ApproachCountingpulsesPositive direction of travelActual value wh

Página 120

Positioning IP 240If you configured the channel with DAV=2 (the IP controls the direction of travel duringpositioning) and want to pass control of t

Página 121

IP 240 Positioningb) If the IP outputs are to be controlled by the module firmware (HAND=0), they can beenabled immediately (FREI=1).If the IP 240 c

Página 122

Positioning IP 240Switching the IP outputs during reference point approach (HAND=0)The switching performance of the IP outputs specified when the ch

Página 123

IP 240 Positioningc) DAV=2After the outputs have been enabled, the IP output specified by setting control bit DA1S orDA2S is set.The output is reset

Página 124

IP 240 Module Description and Accessories 5 Vsym.pulse trainA, A, B, B, Z, Z 5 VA*, B*, Z*IN, CLK, GT 24 VA*, B*, Z*IN, CLK, GTData for rated voltag

Página 125

Positioning IP 240Status of range bits BEE1, BEE2 and BEE3 during reference point approachWhen reference point approach is selected, all three range

Página 126 - 8 Counting

IP 240 PositioningInterrupting a reference point approachYou can interrupt a reference point approach by transferring• control bit HASY = 0 or• cont

Página 127 - Counting IP 240

Positioning IP 240The new position number can be transferred to the IP 240 together with SOSY=1. Refer toSection 10.14.1 for information on how to s

Página 128 - 8.2.3 Forcing the IP Output

IP 240 Positioning10.13.3 Synchronization with an External Control SignalWhen synchronization with an external control signal, referred to from here

Página 129

Positioning IP 240Fig. 10-29. Synchronization with an External Control Signal at the IN InputSample actual valueNew actual valueOld ControlbitZYSY

Página 130 - IP 240 Counting

IP 240 PositioningWarningCyclic synchronization is also allowed when the IP outputs are set. The positiontransferred goes into force immediately on

Página 131

Positioning IP 24010.14 Selecting a PositionPositioning is started by selecting a position. The IP 240 uses the position value for the positionselec

Página 132

IP 240 PositioningNoteThe IP 240 accepts the specified position number only when control bit HAND is notset. In addition,• status bit SYNC must be s

Página 133

Positioning IP 240If it is necessary to disable the IP outputs, you can do so by transferring FREI=0 and, at the sametime, specify the new position

Página 134

IP 240 PositioningTable 10-18. Contents of the DB and the Transfer Buffer for Writing Position 0Bit76543210DescriptionData byteDatablockOffsetin t

Página 135

Module Description and Accessories IP 240Digital outputsNumber of outputs 4 (2 per channel)Galvanic isolation yesin groups of 1Supply voltage VpRa

Página 136 - 8.3.2 Control Function Block

Positioning IP 24010.15 Controlling the Digital Outputs During PositioningYou can use IP outputs D1 and D2 to• change the traversing speed or• contr

Página 137

IP 240 PositioningControlling the IP outputs via the S5 CPU (HAND=1)You can define the states which the IP outputs are to assume via the S5 CPU usin

Página 138

Positioning IP 240Table 10-19. Contents of the DB and the Transfer Buffer for Transferring the Control Bits Bit76543210DescriptionData byteDatab

Página 139

IP 240 Positioning10.16 Reading and Evaluating the IP Status InformationThis includes:• the current (feedback) position number• the status bits• the

Página 140

Positioning IP 240Reading the status information from the IP 240with control FB 168 in direct data interchangeYou must initialize FB 168 as follows

Página 141

IP 240 PositioningBit is ”0”Status bit Bit is ”1”ZBEV(target rangeexited)BEE1BEE2BEE3PositioningBEE1BEE2BEE3Referencepoint BEE1approach(HASY=1)BEE2P

Página 142

Positioning IP 240Status bitActual value exited range BEE2. Rever-sal of direction of travel is possible.RIUM(Reversal ofdirection)A new position nu

Página 143

IP 240 PositioningWhen they have been read, status bits NPUE, UEBL, MESE and UEBS are reset on the IP 240, i.e.these bits can be read out only once.

Página 144

Positioning IP 240Table 10-21. Contents of the DB and the Transfer Buffer on Reading the Interrupt Request Bytes Bit76543210DescriptionData byte

Página 145

IP 240 PositioningExamples for interrupt bits BE1 to BE3, ZBV and RIUWithoutbacklashcompensationTargetpositionLinearaxisRotary axisPositivedirection

Página 146

IP 240 Module Description and AccessoriesEncoder supplyThe power supply for 5 V encoders is taken from the programmable controller's power supp

Página 147

Positioning IP 240Interrupt bit Bit is ”1”UEB(Overflow)The actual value has exited the valid actual value range and entered theoverrange.MESUBS

Página 148

IP 240 PositioningThe modified data go into force as soon as they are transferred. The IP 240 updates the status bitsand generates any pending inter

Página 149

Positioning IP 240If you use FB 168 to write the new position values, you must specify the entry to be transferred inthe data block when you initial

Página 150

IP 240 Positioning10.18.2 Changing the Distance Values for Ranges BEE1 to BEE3Table 10-23. Contents of the Data Block and the Transfer Buffer for

Página 151

Positioning IP 240Transferring modified distance values for the switching and signalling rangeswith control FB 168 in direct data interchangeYou mus

Página 152

IP 240 PositioningTable 10-24. Contents of the Data Block and the Transfer Buffer for Changing the Zero OffsetZero offset in binaryA negative valu

Página 153

Positioning IP 24010.19 Interrupting Positioning and Skipping of a PositionPositioning is interrupted when• control bit FREI=0 is transferred.In thi

Página 154

IP 240 PositioningIf the channel was structured for backlash compensation and the actual position is above thetarget position (RICH=1), output D2 is

Página 155

Positioning IP 24010.21 Positioning with the IP 240The flowchart below illustrates the functional sequence for positioning with the IP 240.In the ex

Página 156 - 9 IP 252 Expansion

IP 240 Positioning10.21.2 Positioning with the IP Controlling the DirectionFig. 10-32. Positioning with the IP 240 Controlling the Direction of Trav

Página 157 - IP 252 Expansion IP 240

Module Description and Accessories IP 2402.4 Order NumbersOrder No.Module without instruction manual 6ES5 240-1AA21Adapter casing for 2 modules in

Página 158 - IP 240 IP 252 Expansion

Positioning IP 24010.22 Error Processing Following Positioning ControlErrors occurring during transfer of data to the IP are flagged• in the PAFE by

Página 159 - YOU must

IP 240 Positioning10.23 Data Block Contents and Initializing the Standard Function Blocks10.23.1 The Data BlockCreating the data blockThe standard f

Página 160

Positioning IP 240Contents of the data blockTable 10-27. Contents of the Data Block (DW 0 to DW 821)DW 59Final position of the rotaryaxisDW 45 to

Página 161

IP 240 PositioningContents of the data wordsYou must set the unassigned positions of the data words you want to transfer to the IP 240 to ”0”.Functi

Página 162 - 9.4.2 Data Block Contents

Positioning IP 240ID for the configured mode and data block numberDL 23DR 237Databyte6 5 4 3 2 1 0025024023122021020Bit027026DB no.Following error-f

Página 163

IP 240 PositioningStatus bitsDatabyte7DL 29DR 296 5 4 3 2 1 0Bit0DA20DA1RIUMMESEZBEVBEE3UEBSBEE2DRBRBEE1NPUERICHUEBLSYNCRIUM = 1 Range BEE2 was exit

Página 164

Positioning IP 240Final valueSE21821022SE2172921SE2162820Binary representation BCD representationDL 32DR 32DL 33DR 33SE22021224106104102100SG1051031

Página 165

IP 240 PositioningData for position 0Position value for position 0SE21921123SE21821022SE2172921SE2162820Binary representation BCD representationDL 3

Página 166

Positioning IP 240DL43DR437Databyte6 5 4 3 2 1 02132521224211232102229212820Bit2152721426Distance value for range BEE3DL44DR447Databyte6 5 4 3 2 1 0

Página 167 - 10 Positioning

IP 240 PositioningFinal position of the rotary axis 021921123 021821022 02172921 02162820Binary representation BCD representationDL 48DR 48DL 49DR 4

Página 168 - 10.1.2 Functional Description

4 Hardware Installation5 Operation6 Functional Description7 Position Decoding8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Interchange with

Página 169 - IP 240 Positioning

Positioning IP 240Position number and position value for positions 1 to 254In the tables below, the first word for a position entry is always identi

Página 170 - Positioning IP 240

IP 240 Positioning10.23.2 The Configuring Function BlockFB 167 (STRU.POS) Configures and initializes the IP 240 for ”positioning” modeFunctional des

Página 171

Positioning IP 240Table 10-28. Parameters for Configuring FB 167NAMEParametertypeDatatypeDescriptionBGADKANRDBNRAFLIMPBCDPRA1PRA2RUNDLOSEDAVPAFEBE

Página 172

IP 240 PositioningBCD : KY x,y Number formatx /y=0 Binary x /y=1 BCDx determines the following values:• Position values for positions 1 to 254• Dist

Página 173 - Switching the IP outputs

Positioning IP 240PAFE : QB QB or FY (0 to 239) for flagging errors ( Section 6.4)BER : KF 0 Addressing in P area1 Addressing in Q areaABIT : KYx,y

Página 174

IP 240 PositioningTechnical SpecificationsBlock number : 167Block name : STRU. POSAG Library numberCall length/Block lengthCPU Processing time 1S5-1

Página 175

Positioning IP 24010.23.3 The Control Function BlockFB 168 (STEU.POS) Control function block for ”positioning” modeFunctional DescriptionThe control

Página 176 - 10.3 Numerical Representation

IP 240 PositioningInvoking the control function blockThe control FB is normally invoked in the cyclic program and in the interrupt service OBs.Name

Página 177

Positioning IP 2403 - Read interrupt request bytes41 1 to Transfer position value for the yth entry in the DB.255 y= Entry to be transferred42 1 to

Página 178 - - Actual value

IP 240 PositioningTechnical SpecificationsBlock number : 168Block name : STEU. POSAG Library numberCall length/Block lengthCPUProcessing time1Functi

Página 179

Figures3-1. Locations of the Address Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 1EWA 4NEB 811 6120-02a

Página 180 - 10.4.1 Linear Axis

Positioning IP 24010.24 Sample Program for Processing Data Words with a Data Word NumberExceeding 255If a data block exceeds a length of 256 data wo

Página 181 - 10.4.2 Rotary Axis

IP 240 Positioning**************************SAMPLE PROGRAM FOR S5-115U**************************NAME :L/T DWXID :DBNR I/Q/D/B/T/C: D KM/KH/KY

Página 182

Positioning IP 240***********************************SAMPLE PROGRAM FOR S5-135U AND 150U***********************************ADDRESS REQUIRED IN PROGR

Página 183 - 10.5 Switching the IP Outputs

IP 240 Positioning**************************SAMPLE PROGRAM FOR S5-155U**************************THE ADDRESS REQUIRED IN THE PROGRAMDEPENDS ON THE DA

Página 184

Positioning IP 24010.25 Example: Removing Parts from a Die-Casting MachineFinished parts are to be taken from a die-casting machine and deposited at

Página 185

IP 240 PositioningFlags, inputs, outputs, timers and DBs OPERAND SYMBOL COMM

Página 186

Positioning IP 240OPERAND SYMBOL COMMENTARYFY 65 ERROR REASON FOR SETTING GROUP ERROR FLAG (F 64.7)F 65.0 ERR00 REF. POINT APPROACH TERM. WITHOUT SY

Página 187

IP 240 PositioningOPERAND SYMBOL COMMENTARYFY 200 PAFE CONTENTS SEE INSTR. MAN. SEC. 6.4T 1 POSTIMER WATCHDOG TIMER FOR POSITIONINGT 2 STOPTIMER TIM

Página 188

Positioning IP 240Functional sequence:yesRestart routine (FB 20)START”Start”?Configure IP 240:- Channel 1 for positioning modeCompute reference poi

Página 189 - 10.7 Actual Value Generation

IP 240 PositioningCyclic program for x axis (FB 30)yesnonononoMain switch on?STARTRefe-rence point approach exe-cuted?ENDRead actual value and statu

Página 190 - 10.7.1 Resolution (AFL)

IP 240 Addressing3 AddressingThe IP 240 module reserves an address space of 16 bytes in the I/O areas. All data are exchangedvia these areas, which

Página 191 - · Specified resolution

Positioning IP 240Reference point approach FB 31yesnoyesReference point approach in progress?STARTReset IP outputsPreselect negative directionSelect

Página 192 - 10.7.2 Zero Offset

IP 240 PositioningSelect next position (FB 32)yes- Prepare for ”open gripper”- Write next eject position to transferflag- Decide whether machining c

Página 193

Positioning IP 240Select and approach position (FB 33)Transfer position number and controlbits (FREI = "1") to IPRead out status from IP n

Página 194 - = - 2,000

IP 240 PositioningInterrupt service routine for x axis (FB 34)STARTStart watchdog timer for motordecelerationnoCut-off range entered?yesTarget range

Página 195

Positioning IP 240DB100 TRAVERSING DATA ##################################

Página 196

IP 240 Positioning DB128 0: KH = 0000; 1: KS =&a

Página 197

Positioning IP 240 69: KH = 0004; 4TH POS. NO. 70: KH = 0025; ] 4TH VALUE 71: K

Página 198

IP 240 PositioningFB 20 NETWORK 1 0000

Página 199

Positioning IP 240FY 60 = NPOS NO. OF NEXT POS. TO BE APPROACHEDFY 61 = RESPONSE RESPONSE WHEN POSITION

Página 200

IP 240 PositioningNETWORK 5 0051 RELOAD SCRATCH FLAGS / RS DATA0051 : ------------------------

Página 201

Addressing IP 240Switch settingsI/O area(P)extendedI/O area(Q)I/O area1281441601761922082242400163248648096112144128160176192208224240Startingaddres

Página 202

Positioning IP 240FB 30 NETWORK 1 0000

Página 203

IP 240 PositioningI 32.0 = MAINSW MAIN SWITCH: ENABLE FOR CONTROL SYSTEMF 0.0 = RLO0 FLAG FOR "0&q

Página 204

Positioning IP 240F 64.2 = REFACTIV REF.POINT APPROACH IN PROGRESSF 64.0 = POSACTIV POSITIONING IN PROGRESSQ

Página 205

IP 240 Positioning0082 :0083 :A I 33.2 -GRUP LIMIT SWITCH MONITORING0084 :R Q 5.1 -CLOSGR GR

Página 206

Positioning IP 240FB 31 NETWORK 1 0000#

Página 207

IP 240 Positioning0042 :JU FB 1680043 NAME :STEU.POS0044 DBNR : KF +00045 FKT : KY 20,0 TRANSFER CONTROL BITS00

Página 208

Positioning IP 240FB 32 NETWORK 1 0000#

Página 209

IP 240 PositioningFB 33 NETWORK 1 0000##

Página 210

Positioning IP 2400041 :0042 :A F 63.3 -BEE20043 :A F 63.1 -RICH0044 := Q 4.1 -NEGPOS0045 :JC =NTW2

Página 211

IP 240 PositioningNETWORK 2 0061 ERROR MONITORING0061 :A T 1 -POSTIMER WHEN TIME EXCEEDED0062 :S F 6

Página 212

IP 240 AddressingUse of the IP 240 in the S5-183U, S5-184U, S5-185U and S5-186U expansion unitsIf you use the IP 240 in one of these EUs, set the st

Página 213

Positioning IP 240FB 34 NETWORK 1 0000#

Página 214 - a

IP 240 PositioningNETWORK 3 0031 CUT-OFF RANGE REACHED0031 :AN F 69.3 -BE20032 :JC =NTW30033 :A F 0.1 -RLO10

Página 215

Positioning IP 240NETWORK 6 0051 HARDWARE FAULTS0051 :AN F 68.0 -UEB0052 :AN F 68.1 -NPU0053 :AN F 68.2 -DR

Página 216 - 10.14 Selecting a Position

IP 240 PositioningFB 167 NETWORK 1 0000

Página 217

Positioning IP 240OB 2 NETWORK 1 0000

Página 218 - 10.14.2 Selecting Position 0

11 Direct Data Interchange with the IP 24011.1 Status and Job Request Register (Offset 15) . . . . . . . . . . . . . . . . . . . . . 11 - 211.1.1 Stat

Página 219

Figures11-1. Flowchart for ”Read data from the IP 240” . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11- 511-2. Flowchart for ”Write data to

Página 220

IP 240 Direct Data Interchange with the IP 24011 Direct Data Interchange with the IP 240For time-critical applications, it may be necessary to excha

Página 221

Direct Data Interchange with the IP 240 IP 240In the following, it has been assumed that the channel has been configured with standard FB 167for pos

Página 222

IP 240 Direct Data Interchange with the IP 240Table 11-1. Contents of the Status RegisterBit Abbr. Meaning when bit is ”1”Job terminated,The job

Página 223

IP 240 Replacement Pages for IP 240 Manual, Edition 3Supplement to the IP 240 Manual, Order No. 6ES5 998 0TB22, Edition 3Use of the IP 240 in the S7-

Página 224

5 Operation6 Functional Description7 Position Decoding8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Interchange with the IP 24012 Response

Página 225

Direct Data Interchange with the IP 240 IP 24011.1.2 Job Request RegisterThe S5 CPU enters the job number in the job request register, thus telling

Página 226

IP 240 Direct Data Interchange with the IP 24011.2 Data Transfer from the IP 240 to the S5 CPUThe S5 CPU can request data from the IP 240. To make t

Página 227

Direct Data Interchange with the IP 240 IP 240Fig. 11-1. Flowchart for ”Read Data from the IP 240” (Continued)EndnonoyesError detected?Data not ye

Página 228

IP 240 Direct Data Interchange with the IP 24011.3 Data Transfer from the S5 CPU to the IP 240The S5 CPU can forward new data to the IP 240. To do s

Página 229

Direct Data Interchange with the IP 240 IP 240The flowchart shown below illustrates the communication procedure for ”Write data to theIP 240”Fig. 11

Página 230

IP 240 Direct Data Interchange with the IP 240Fig. 11-2. Flowchart for ”Write Data to the IP 240” (Continued)nononoyesError detected?Data not yet

Página 231 - DR n+3

Direct Data Interchange with the IP 240 IP 24011.4 Contents of the Transfer Buffer11.4.1 Position Decoding ModeRead actual value and status areaWhen

Página 232 - : JU FB 168

IP 240 Direct Data Interchange with the IP 240SYNC =1 Reference point approach was terminated with synchronizationDRBR =1 Wirebreak/short-circuit in

Página 233

Direct Data Interchange with the IP 240 IP 240Write initial and final track valuesTo change the initial value and final value for a track, you must

Página 234

IP 240 Direct Data Interchange with the IP 240Write control bitsTo initialize control bits, you must load the new control bits into the transfer buf

Página 235

Figures4-1. Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 44-2. Con

Página 236

Direct Data Interchange with the IP 240 IP 24011.4.2 Counting ModeRead actual value, final value and status areaThe IP 240 makes the actual value, t

Página 237

IP 240 Direct Data Interchange with the IP 240REF2 =1 Final value was storedUEBL =1 Actual value out of range (<- 9,999)UEBE =1 Final value out o

Página 238

Direct Data Interchange with the IP 240 IP 240Write initial countTo modify the initial count value, you must enter the new value in the transfer buf

Página 239

IP 240 Direct Data Interchange with the IP 24011.4.3 Reading Error MessagesThe IP 240 makes the error available in the transfer buffer when you tran

Página 240

Direct Data Interchange with the IP 240 IP 24011.5 Sample ProgramsThe following sample programs show how to program direct data interchange with the

Página 241 - 10.23.1 The Data Block

IP 240 Direct Data Interchange with the IP 240: L M 239.4 -ERR ERROR?: JC =ERR2 JUMP TO ”READ ERROR MESSAGES”:: L PY224 TRANSFER BCD-CODED ACTUAL V

Página 242 - DW 32 to

Direct Data Interchange with the IP 240 IP 24011.5.2 Writing Data to the IP 240The module is set to module address 160 and channel 2 is configured f

Página 243

IP 240 Direct Data Interchange with the IP 240 : L FY 142 TRANSFER BCD DECADES 10^3 AND 10^2 : T PY 161 OF THE INITIAL VAL. FOR THE 3RD TR

Página 244

Direct Data Interchange with the IP 240 IP 240ERR3 : L KH0001 LOAD JOB NUMBER FOR ”LOAD ERROR: T PY175 MESSAGES” AND TRANSFER JOB NO.:STA5 : L PY175

Página 245

12 Response Times12.1 Structure of a Firmware Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 - 112.2 Computing the Respons

Página 246

IP 240 Hardware Installation4 Hardware Installation4.1 Installation4.1.1 Suitable Programmable Controllers and Expansion UnitsThe IP 240 can be used

Página 247

12-1. Firmware Execution Times, Position Decoding Mode . . . . . . . . . . . . . . . . . . . 12 - 412-2. Firmware Execution Times, Counting Mode . . .

Página 248 - = 0 Relative zero offset

IP 240 Response Times12 Response TimesThe response time is the time between reaching of a setpoint and the IP 240's reaction.The signals from t

Página 249

Response Times IP 24012.2 Computing the Response TimeUsing channel 1 as example, Figure 12-2 shows which FW slices must be taken into account whenco

Página 250

IP 240 Response Times Fig. 12-3. Response Time for Evaluation of the Actual Value and of Wirebreakand Zero Mark ErrorsSetpoint reachedor error hasoc

Página 251

Response Times IP 24012.3 Firmware Execution TimesThe execution time of the individual firmware slices depends on• the modes in which the channels a

Página 252

IP 240 Response TimesChannel 2: • Base time without configuring tA=45µs• Position decoding mode tWW= 520 µs• 8 tracks used, without hysteresis 8 x t

Página 253 - • Actual value

Response Times IP 240Positioning modeTable 12-3. Firmware Execution Times, Positioning ModeDescriptionBase time without configuring 45 µsAbbrev.Ma

Página 254

13 Encoder Signals13.1 Signal Forms and Timing Requirementsfor Incremental Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 255

13-1. Signal Forms: Symmetrical Encoder Signals A/A, B/B, Z/Z andAsymmetrical Encoder Signals A*, B*, Z* . . . . . . . . . . . . . . . . . . . . . . .

Página 256

IP 240 Encoder Signals13 Encoder SignalsThis section discusses the requirements for the forms and timing of the signals for the IP 240. Thefollowing

Página 257

Hardware Installation IP 240S5-115U expansion unit, ER 701-3 subrack7PS IM0 1 2 3 4 5 6NoteIf the IP 240 is operated in an ER 701-3 expansion unit,

Página 258 - Format Description

Encoder Signals IP 24013.1.2 Timing RequirementsThe following diagrams show the timing requirements for signals A, B and Z at the IP 240's inpu

Página 259

IP 240 Encoder SignalsFig. 13-2. Timing Diagram for Symmetrical Incremental Encoders (Continued)A signalA signalB signalB signalZ sign.1)Z sign.Z

Página 260 - Exceeding 255

Encoder Signals IP 240Timing requirements for encoders with asymmetrical signalsFig. 13-3. Timing Diagram for Asymmetrical Encoderst5t51) Position

Página 261

IP 240 Encoder SignalsThe IN signal is evaluated by the IP 240 module firmware. For this reason, acquisition of the signaledges may sometimes be def

Página 262

Encoder Signals IP 240Connecting the synchronization signal to the IN inputFig. 13-6. Timing Diagram for the Synchronization Signal, Positioning M

Página 263

14 Error Messages14.1 Hardware Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 114.2 Error Messa

Página 264

14-1. Errors Flagged in the PAFE Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 114-2. Hardware Faults . . . .

Página 265

IP 240 Error Messages14 Error MessagesIf you use standard FBs 167 to 173 for data interchange between S5 CPU and IP 240, you canascertain whether an

Página 266

Error Messages IP 24014.2 Error Messages in Position Decoding and Counting Mode14.2.1 Parameter and Data ErrorsIn position decoding and counting mod

Página 267

IP 240 Error Messages14.2.2 Communications ErrorsCommunications errors can occur when you interchange data directly with the IP 240 withoutusing con

Página 268

IP 240 Hardware InstallationS5-183U expansion unit 1)3 15511 19 27 35 43 51 59 67 75 83 91 107 123 131 139 14799 115 163S5-184U expansion unit 1)155

Página 269

Error Messages IP 24014.4.2 Data ErrorsThe specified data is checked by the module firmware. If standard function blocks are used fordata interchang

Página 270

IP 240 Error MessagesTable 14-7. Data Errors in Positioning Mode (Continued)Chan. 1DescriptionExten-sionChan. 2Error code for60 90 nn Position num

Página 271

Error Messages IP 240Table 14-7. Data Errors in Positioning Mode (Continued)DescriptionExten-sionChan. 2Chan. 1Error code forMore than one synchro

Página 272

A-1IP 240EWA 4NEB 811 6120-02bAdapter Casing (S5 Adapter)In this chapter, you will learn how to install modules in the adapter casing, and what you

Página 273

A-2IP 240EWA 4NEB 811 6120-02bA.1 PrerequisitesThe following prerequisites must be observed as regards the use of S5modules in the S7-400: Check with

Página 274

A-3IP 240EWA 4NEB 811 6120-02bA.2 Installing an Adapter Casing in the S7-400To install an S5 module in an S7-400, you must first install the adapter c

Página 275

A-4IP 240EWA 4NEB 811 6120-02bA.3 Inserting S5 Modules in the Adapter CasingProceed as follows to insert an S5 module in the adapter casing:1. Set an

Página 276

A-5IP 240EWA 4NEB 811 6120-02bA.4 Interrupt ProcessingThe adapter casing converts S5 interrupts into S7 interrupt functions and in-terrupt signals.All

Página 277

A-6IP 240EWA 4NEB 811 6120-02bA.5 Technical SpecificationsDimensions and WeightDimensions WHD 50mm290mm210mm(1.96 in. x 11.41 in. x8.26 in.)Weight

Página 278

B-1IP 240EWA 4NEB 811 6120-02bAddressing S5 Modules (Adapter Casing and IM 463-2)This chapter describes how to address S5 modules inserted in the ada

Página 279

Hardware Installation1P 2404.2 Wiring4.2.1 Wiring MethodII~ Base connector Xl,Submin. D-type socket connector (1 5-pin)X2 and X4ShieldFixing screw, 4-

Página 280

B-2IP 240EWA 4NEB 811 6120-02bB.1 Addressing S5 ModulesThere are two ways of using an IP xxx S5 module in the S7-400: By installing it in the adapter

Página 281

B-3IP 240EWA 4NEB 811 6120-02bS5 modules in the S7-400 may be addressed in the following addressingareas: I/O area (P area) Extended I/O area (Q, IM

Página 282

B-4IP 240EWA 4NEB 811 6120-02bThe CPU and an IP (an IP being an intelligent I/O module) interchange datavia the S5 bus interface and a 2 Kbyte dual-po

Página 283

C-1IP 240EWA 4NEB 811 6120-02bThe IP 240 Counter, Position Decoder andPositioning ModuleThis chapter describes the counting, position decoding and pos

Página 284

C-2IP 240EWA 4NEB 811 6120-02bC.1 OverviewThis addendum supplements Chapters 7, 8 and 10 of the Manual. It describesthe standard functions of the IP 2

Página 285

C-3IP 240EWA 4NEB 811 6120-02bResult:The software is installed in the following directories on the target drive:Software DirectoryCounting and positio

Página 286

C-4IP 240EWA 4NEB 811 6120-02bC.2 Counting FunctionsFunction FC 171 (STRU_DOS)The call, meaning and parameter values for the FC 171 function are de-s

Página 287

C-5IP 240EWA 4NEB 811 6120-02bFunction FC 172 (STEU_DOS)The call, meaning and parameter values for the FC 172 function are de-scribed below.Ladder Dia

Página 288

C-6IP 240EWA 4NEB 811 6120-02bThe technical specifications for FC 171 and FC 172 are listed below:FC 171 FC 172Block number 171 172Block name STRU_DOS

Página 289

C-7IP 240EWA 4NEB 811 6120-02bC.3 Position Decoding FunctionsFunction FC 164 (STRU_WEG)The call, meaning and parameter values for the FC 169 function

Página 290

IP240Hardware Installation4.2.2 Connector Pin AssignmentsFront Connector Pin AssignmentsX21X46‘ 15014013012011010 c), 90706050403020X31X5X6–A—ii–M—B–E

Página 291

C-8IP 240EWA 4NEB 811 6120-02bFunction FC 170 (STEU_WEG)The call, meaning, and parameter values for the FC 165 function are de-scribed below.Ladder Di

Página 292

C-9IP 240EWA 4NEB 811 6120-02bThe technical specifications for FC 169 and FC 170 are listed below:FC 169 FC 170Block number 169 170Block name STRU_WEG

Página 293

C-10IP 240EWA 4NEB 811 6120-02bC.4 Positioning FunctionsFunction FC 167 (STRU_POS)The call, meaning, and parameter values for the FC 167 function are

Página 294

C-11IP 240EWA 4NEB 811 6120-02bDBNR: INT = xx = Depends on the CPU used (0 is not permitted)For the values of all other parameters, please refer to t

Página 295

C-12IP 240EWA 4NEB 811 6120-02bThe technical specifications for FC 167 and FC 168 are listed below:FC 167 FC 168Block number 167 168Block name STRU_PO

Página 296

C-13IP 240EWA 4NEB 811 6120-02bC.5 Differences between SIMATIC S7 and SIMATIC S5As a rule, the following applies for SIMATIC S7: The memory locations

Página 297 - With offset 15 you address:

C-14IP 240EWA 4NEB 811 6120-02bC.6 Programming Example for “Counting” ModePrerequisites, Settings, Blocks and AddressesThe programming example describ

Página 298 - 11.1.1 Status Register

C-15IP 240EWA 4NEB 811 6120-02bThe following interrupt settings are required in the CPU: Process interrupt: OB 40, Interrupt: I1 (S5 assignment: IA)

Página 299

C-16IP 240EWA 4NEB 811 6120-02bThe inputs and outputs are mapped onto memory bits at the beginning andend of OB 1. Within the test program, only the m

Página 300 - Read error codes

C-17IP 240EWA 4NEB 811 6120-02bStart-up Program and Error ResponsesThe start-up program is located in OB 100. When OB 100 has been pro-cessed, you can

Página 301 - IDLE=1?

Hardware Installation IP 240Shielding of cable connections on the IP 240WarningTo ensure noise immunity, shielded twisted-pair cables must be used f

Página 302

C-18IP 240EWA 4NEB 811 6120-02bCyclic ProgramThe cyclic program is located in OB 1.At the beginning of the program, the inputs are mapped to memory bi

Página 303

C-19IP 240EWA 4NEB 811 6120-02bInterrupt ProgramThe interrupt program is located in the organization block OB 40.In the start-up program, the module i

Página 304

C-20IP 240EWA 4NEB 811 6120-02bC.7 Programming Example for “Position Decoding” ModePrerequisites, Settings, Blocks and AddressesThe programming exampl

Página 305

C-21IP 240EWA 4NEB 811 6120-02bThe following interrupt settings are required in the CPU: Process interrupt: OB 40, Interrupt I1 (S5 assignment: IA).

Página 306 - 11.4.1 Position Decoding Mode

C-22IP 240EWA 4NEB 811 6120-02bThe inputs and outputs are mapped onto memory bits at the beginning andend of OB 1. Within the test program, only the m

Página 307

C-23IP 240EWA 4NEB 811 6120-02bStart-up Program and Error ResponsesThe start-up program is in OB 100. When OB 100 has been processed, youcan check the

Página 308

C-24IP 240EWA 4NEB 811 6120-02bCyclic ProgramThe cyclic program is in OB 1.At the beginning of the program, the inputs are mapped to memory bitswhich

Página 309

C-25IP 240EWA 4NEB 811 6120-02bThe LEDs in the front panel allow you to observe the setting of the digitaloutputs D1 and D2 on the module.With the DIG

Página 310 - 11.4.2 Counting Mode

C-26IP 240EWA 4NEB 811 6120-02bInterrupt ProgramThe interrupt program is located in the organization block OB 40.In the start-up program, the module i

Página 311

C-27IP 240EWA 4NEB 811 6120-02bC.8 Programming Example for “Positioning” ModePrerequisites, Settings, Blocks and AddressesThe programming example desc

Página 312

IP 240 Hardware Installation4.3 Installation Examples4.3.1 InputsFig. 4-3. Connection of BERO Proximity SwitchesA1 has NO function (”1” signal)A2

Página 313 - 11.4.3 Reading Error Messages

C-28IP 240EWA 4NEB 811 6120-02bThe following interrupt settings are required in the CPU: Process interrupt: OB 40, Interrupt I1 (S5 assignment: IA).

Página 314 - 11.5 Sample Programs

C-29IP 240EWA 4NEB 811 6120-02bThe inputs and outputs are mapped onto memory bits at the beginning andend of OB 1. Within the test program, only the m

Página 315

C-30IP 240EWA 4NEB 811 6120-02bStart-up Program and Error ResponsesThe start-up program is in OB 100. When OB 100 has been processed, youcan check the

Página 316

C-31IP 240EWA 4NEB 811 6120-02bCyclic ProgramThe cyclic program is in OB 1.At the beginning of the program, the inputs are mapped to memory bitswhich

Página 317

C-32IP 240EWA 4NEB 811 6120-02bWith the control word DB 168.DBW 38 FUNCTION = B#(21,1)and brief activation of the input I 1.0 (M190.0), position 1 is

Página 318

C-33IP 240EWA 4NEB 811 6120-02bThe LEDs in the front panel allow you to observe the setting of the digitaloutputs D1 and D2 on the module.With the DAV

Página 319

C-34IP 240EWA 4NEB 811 6120-02bInterrupt ProgramThe interrupt program is located in the organization block OB 40.In the start-up program, the module i

Página 320

IndexEWA 4NEB 811 6120-02a

Página 321 - 12 Response Times

IP 240 IndexIndexAABIT 7-15, 10-36, 10-85,10-86, 10-88Actual value 7-3, 8-3, 10-23,10-28, 10-57, 10-61,10-76, 10-79- acquisition 7-17, 7-26, 10-26-

Página 322 - Response Times IP 240

Index IP 240Communication 11-2- cycle 11-2, 11-7- errors 6-6, 7-25, 8-13, 9-7,10-36, 14-1, 14-3,14-6- error flags 6-6- resetting 11-8, 11-9- start 1

Página 323 - IP 240 Response Times

Hardware Installation IP 240Incremental Encoders(with symmetrical outputs to RS 422 A)Fig. 4-4. Connection of Encoders with Symmetrical Output Sig

Página 324 - 12.3 Firmware Execution Times

IP 240 IndexDD subminiature socket connector 2-4DA1 7-13, 7-26, 8-4, 8-5,8-14, 11-10, 11-14DA1F 7-26, 8-3, 8-14,11-13, 11-16DA1S 7-26, 8-3, 8-4, 8-1

Página 325

Index IP 240Encoder- signal 2-2, 2-4, 4-8 ... 4-10,5-7, 6-1- signal forms 13-1- signal level 5-7- signal matching 5-1- supply 2-2, 2-4, 2-7, 5-1- su

Página 326

IP 240 IndexHHardware 7-18- fault 2-7, 6-3, 6-6, 10-36,14-1- fault flag/code/message 6-6, 14-1- version 7-18, 8-7, 9-5, 10-85HOLD time 13-7HW Hard

Página 327

Index IP 240JJob request 11-4- identified 11-3- identifier 11-11- number 10-37, 10-61, 10-74,11-1, 11-4, 11-7- register 11-1, 11-2, 11-4,11-5, 11-7,

Página 328

IP 240 IndexParameter 10-86, 10-91, 14-3- assignment 7-18, 8-7, 10-85- assignment errors 6-6, 6-7, 7-18, 7-23,7-25, 8-7, 8-11, 8-13,9-5, 9-7, 14-1,

Página 329 - 13 Encoder Signals

Index IP 240REF1 11-14REF2 8-3, 11-15REF bit 7-5, 7-6, 7-14, 8-5Reference- bit 7-15, 7-20, 8-8, 8-15- signal 2-2, 7-16- tracks 7-1, 7-4, 7-5, 7-8,7-

Página 330 - 13.1.2 Timing Requirements

IP 240 IndexStatus bit- DRBR 7-14, 10-33, 10-60,10-79- MESE 10-47, 10-60, 10-79- NPUE 10-34, 10-60, 10-79- RICH 10-5, 10-18, 10-59,10-79- RIUM 10-60

Página 331 - IP 240 Encoder Signals

Index IP 240Write- control bit 10-90- modified distance values 10-90- modified position values 10-90- modified zero offset 10-90- position data for

Página 332 - Encoder Signals IP 240

IP 240 Module Description and Accessories2 Module Description and Accessories2.1 General Technical SpecificationsTemperatureOperation 0 to +55 °C(In

Página 333

Module Description and Accessories IP 2402.2 Technical SpecificationsThe IP 240 has two independent channels. In the IP 252 expansion mode, the enc

Página 334

12345678PrefaceIntroductionAddressingHardware InstallationOperationFunctional DescriptionPosition DecodingCountingIP 252 Expansion 9Module Description

Página 335 - EWA 4NEB 811 6120-02 a

IP 240 Hardware InstallationIncremental Encoders(with asymmetrical outputs)Fig. 4-5. Connection of Encoders with Asymmetrical Signals: Push-Pull Enc

Página 336

IP 240 Module Description and AccessoriesInput frequencies Pulse inputs:- Symmetrical signals max. 500 kHz in position decoding and positioning mode

Página 337 - 14 Error Messages

Module Description and Accessories IP 2402.2.3 Inputs/OutputsThe IP 240 provides two options for connecting sensors to the pulse inputs:• All senso

Página 338 - Invalid hysteresis

IP 240 Module Description and AccessoriesData for rated voltage 5 V 24 Vsymmetricalpulse trainInput voltage ranges to RS 422 A”0”-Signal - 30to+ 5.

Página 339 - 14.4.1 Parameter Errors

Module Description and Accessories IP 240 Digital outputsNumber of outputs 4 (2 per channel)Galvanic isolation yesin groups of 1Supply voltage VpR

Página 340 - 14.4.2 Data Errors

IP 240 Module Description and AccessoriesEncoder supplyThe power supply for 5 V encoders taken from the programmable controller's power supply

Página 341 - =02 Error on selecting HASY

Module Description and Accessories IP 2402.4 Order NumbersOrder No.Module without instruction manual 6ES5 240-1AA12Adapter casing for 2 modules in

Página 342 - 14.4.3 Communications Errors

IP 240 Addressing3 AddressingThe IP 240 module reserves an address space of 16 bytes in the I/O areas. All data are exchangedvia these areas, which

Página 343 - Adapter Casing (S5 Adapter)

Addressing IP 240Switch settingsI/O area(P)extendedI/O area(Q)I/O area1281441601761922082242400163248648096112144128160176192208224240Startingaddres

Página 344 - A.1 Prerequisites

IP 240 AddressingUse of the IP 240 in expansion units S5-183U, S5-184U, S5-185U and S5-186UIf you use the IP 240 in one of these EUs, set the start

Página 345

IP 240 Operation5 OperationBefore startup you must set various coding switches on the module. You can stipulate• interrupt generation with switchban

Página 346

Hardware Installation IP 240Fig. 4-6. Connection of Encoders with Asymmetrical Signals:Open-Collector Encoder Output CircuitConnectorX2/X4Z*9MB*A*L+

Página 347 - A.4 Interrupt Processing

Operation IP 2405.1 Settings for Interrupt GenerationThe processing of interrupt signals makes it possible to respond rapidly to status changes. In

Página 348 - A.5 Technical Specifications

IP 240 OperationIf several IP 240 modules use one interrupt circuit, the current interrupt source must bedetermined by reading the interrupt request

Página 349 - (Adapter Casing and IM 463-2)

Operation IP 240Fig. 5-3. Allocation of Coding Switches on Switchbanks S1 and S2 to Interrupt Generation with I/O Byte 0PB 0.0 0.1 0.2 0.3 0.4 0.5 0

Página 350 - B.1 Addressing S5 Modules

IP 240 OperationExample for setting the coding switchesThree IP 240s are to be enabled for interrupt generation. One IP 240 is to be operated as mas

Página 351 -  Page area

Operation IP 240Additional programming in the organization blocks for the S5-115U:a) The interrupt service routine must be programmed in an FB so th

Página 352

IP 240 Operation5.3 Matching to Encoder SignalsEncoders with 24 V DC signals and encoders which generate signals to the RS 422 A or a similarstandar

Página 353 - Positioning Module

Siemens AGAUT E 148Postfach 1963D-92209 AmbergFederal Republic of GermanyFrom:Your Name:Your Title:Company Name:Street:City, Zip Code:Country:Please

Página 354 - C.1 Overview

Remarks FormYour comments and recommendations will help us to improve the quality and usefulness ofour publications. Please take the first available o

Página 355 -  Examples:

IP 240 Hardware InstallationSIEMENS provides the following prefabricated cables for connecting a 6FC9320-3..00 incrementalencoder to the IP 240:Cabl

Página 356 - Function FC 171 (STRU_DOS)

Hardware Installation IP 2404.3.2 OutputsFig. 4-8. Connecting the Load to the Digital Outputs on the IP 240+++orVp+VpVpVpX3/X5Vs=Supply voltage((1

Página 357 - Function FC 172 (STEU_DOS)

6 Functional Description7 Position Decoding8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Interchange with the IP 24012 Response Times13 Enc

Página 358 - EWA 4NEB 811 6120-02b

Figures5-1. Locations of Switchbanks and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 1 5-2. Allocation of Coding Sw

Página 359 - Function FC 164 (STRU_WEG)

IP 240 Operation5 OperationBefore startup you must set various coding switches on the module. You can stipulate• interrupt generation with switchban

Página 360 - Function FC 170 (STEU_WEG)

Operation IP 2405.1 Settings for Interrupt GenerationThe processing of interrupt signals makes it possible to respond rapidly to status changes. In

Página 361

IP 240 OperationIf several IP 240 modules use one interrupt circuit, the current interrupt source must be determi-ned by reading the interrupt reque

Página 362 - Function FC 167 (STRU_POS)

Operation IP 240Fig. 5-3. Allocation of Coding Switches on Switchbanks S1 and S2 to Interrupt Generation with I/O Byte 0PB 0.0 0.1 0.2 0.3 0.4 0.5 0

Página 363 - Function FC 168 (STEU_POS)

IP 240 PrefacePrefaceIn addition to open and closed-loop control, the programmable controllers of the SIMATIC S5 fa-mily execute special tasks such

Página 364

IP 240 OperationExample for setting the coding switchesThree IP 240s are to be enabled for interrupt generation. One IP 240 is to be operated as mas

Página 365

Operation IP 240Additional programming in the organization blocks for the S5-115U:a) The interrupt service routine must be programmed in an FB so th

Página 366

IP 240 Operation5.3 Matching to Encoder SignalsYou can connect the following to the IP 240 as position encoders:• symmetrical incremental encoders w

Página 367

7 Position Decoding8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Interchange with the IP 24012 Response Times13 Encoder Signals14 Error Mes

Página 368 - Addresses

Figures6-1. Data Interchange in Programmable Controllers with Multiprocessor Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 369

IP 240 Functional Description6 Functional Description6.1 Module FunctionsThe IP 240 is an intelligent I/O module for acquiring and preprocessing enc

Página 370 - Cyclic Program

Functional Description IP 2406.1.2 Digital OutputsThe digital outputs on the module can be used for direct driving of actuators and displays forpart

Página 371 - Interrupt Program

IP 240 Functional DescriptionWirebreak/short-circuit (red WB LED)When a channel is set to symmetrical pulses, the encoder cable is monitored by eva

Página 372

Functional Description IP 2406.2.1 Configuring Function BlocksConfiguring function blocks serve to select the modes. Each mode is assigned its own f

Página 373

IP 240 Functional Description6.3 Restart Characteristics6.3.1 Power OnAfter ”Power on” a test routine is initiated on the IP 240 to verify proper fu

Página 374

IP 240 IntroductionIntroductionThe following pages contain information which will help you to use this manual.Description of ContentsThe contents of

Página 375

Functional Description IP 240Table 6-2. Error Flagging in the PAFE ByteBit numberPAFE byteError category01237Hardware faults, communication and da

Página 376

IP 240 Functional Description6.4.2 Parameter and Data ErrorsParameter errorsWhen parameter errors occur, the function block sets bit 1 in the PAFE b

Página 377 -  DB 170.DBB 45 Hysteresis

Functional Description IP 2406.5 Multiprocessor OperationIn the S5-135U and S5-115U PLCs with multiprocessor capability,the IP 240 can also be used

Página 378

8 Counting9 IP 252 Expansion10 Positioning11 Direct Data Interchange with the IP 24012 Response Times13 Encoder Signals14 Error Messages7 Position Dec

Página 379

Figures7-1. Counting Direction in Position Decoding Mode . . . . . . . . . . . . . . . . . . . . . . . . 7- 17-2. Actual Value and Overrange in Positi

Página 380

IP 240 Position Decoding7 Position Decoding7.1 ApplicationIn this mode, the IP 240 can be used in all applications in which position changes are to

Página 381

Position Decoding IP 240Changing the counting directionTo change the counting direction, you must interchange the encoder signal connections asfollo

Página 382

IP 240 Position DecodingThe zero offset value thus always offsets the zero point of the actual value range to the referencepoint. A zero offset can

Página 383

Position Decoding IP 240Example:The position encoder emits 1000 pulses/revolution. The spindle has a gradient of 50 mm/revolu-tion. The position enc

Página 384

IP 240 Position DecodingTransfer of the initial values from the data block to the IP 240The limit values are initially transferred to the IP with co

Página 385

Introduction IP 240• Automating with the S5-115USIMATIC S5 programmable controllersHans BergerSiemens AG, Berlin and Munich 1989Contents:- STEP 5 pr

Página 386

Position Decoding IP 240Triggering a process interruptEvery REFn bit can trigger a process interrupt when it goes from 0 to 1 (rising edge). You mus

Página 387

IP 240 Position DecodingIf you set bit DIGn/9 to ”0”, a change in the REF bit from 0 to 1 sets the output only when theactual value enters the track

Página 388 - IP 240 Index

Position Decoding IP 240Fig. 7-4. Evaluating the Reference Tracks1) The interrupt request is reset when the interrupt request bytes are scanned.

Página 389 - Index IP 240

IP 240 Position DecodingTraversing speed and track widthIn order for entry into a track to be detectable in every module firmware cycle, the travers

Página 390

Position Decoding IP 240Defining the hysteresisThe hysteresis can be preset in BCD in the data block in data byte DR 22 ( Section 7.3.3) in therang

Página 391

IP 240 Position DecodingIf the direction is reversed outside the hysteresis range following switching of an output, theswitching point at the track

Página 392

Position Decoding IP 240The output is switched analogously upon entry into and upon exit from the upper track limit.The output is reset when the act

Página 393 - 6-1, 10-12, 10-13

IP 240 Position Decoding7.2.5 Forcing the IP OutputsYou can use control bits DAnF and DAnS (n=1 for digital output 1 or n=2 for digital output 2) to

Página 394

Position Decoding IP 240In addition, the following are carried out on the basis of the specified configuring data:• any outputs that are set are res

Página 395

IP 240 Position DecodingInvoking the interrupt servicing OBs in the S5-150U and S5-155U PLCs (150 mode)In the S5-150U and S5-155U (150 mode), the a

Página 396

IP 240 IntroductionConventionsIn order to improve the readability of the manual, a menu-style breakdown was used, i.e.:• The individual chapters can

Página 397 - 6-1, 7-1 ... 7-3, 7-5

Position Decoding IP 2407.2.9 Reference Point ApproachSince incremental encoders cannot indicate the absolute position after a power failure, a re-f

Página 398 - EWA 4NEB 811 6120-02

IP 240 Position DecodingAborting a reference point approachThe reference point approach initiated by setting the REFF bit is normaly terminated, fol

Página 399

Position Decoding IP 2407.3 Initializing Standard Function Blocks and Data Block Assignments7.3.1 Configuring Function BlockFB 169 (STRU.WEG) Confi

Página 400

IP 240 Position DecodingTable 7-5. Parameters for Configuring FB 169Name Para- Data Descriptionmeter typetypeBGAD D KF Module starting addressKANR

Página 401

Position Decoding IP 240DIG1 : KM 0000 0000 Bit 0 to Bit 7:0000 0000 Assignment of digital output D1 to reference tracks 1 to 8 - Bit n = 1 Output D

Página 402

IP 240 Position DecodingPRA2 : KM 0000 0000 Assignment of a process interrupt to bits in the status area0000 0000 Bit n= 1 A process interrupt is ge

Página 403

Position Decoding IP 240Technical SpecificationsBlock number : 169Block name : STRU. WEGPLC Library numberCall length/Block lengthCPU Processing tim

Página 404

IP 240 Position Decoding7.3.2 Control Function BlockFB 170 (STEU.WEG) Control function block for position decoding mode.Functional descriptionThe co

Página 405

Position Decoding IP 240NoteScratch flags and system data areas are used in the standard function blocks for thepurpose of data interchange with the

Página 406

IP 240 Position Decoding7.3.3 Contents of the Data BlockThe data block to be created must comprise at least 68 words (DW 0 to 67). The number of the

Página 407

Introduction IP 240Manuals can only describe the current version of the programmable controller. Shouldmodifications or supplements become necessary

Página 408

Position Decoding IP 240Control bitsDL 17DR 177Databyte6 5 4 3 2 1 00000DA2F0DA2S0DA1F0DA1SREFFAMSK000BitAMSK =1 All process interrupts for the chan

Página 409 - 5 Operation

IP 240 Position DecodingInterrupt request byte for Channel 1 and Channel 2Channel 1Channel 1Channel 2Channel 2DL 20DR 20DL 21DR 217Databyte6 5 4 3 2

Página 410 - 5.1.1 IRx Interrupt Circuits

Position Decoding IP 240Identifiers of tracks used7 6DL 29DR 29Databyte5 4 3 2 1 00TR60TR50TR40TR30TR20TR1Bit0TR80TR7TRn =1 The track limits for thi

Página 411 - 5.1.2 I/O Byte 0 (PY)

IP 240 Position DecodingFinal value of the first track (END 1)7 6DL 36DR 36DL 37DR 37Databyte5 4 3 2 1 000000Bit00001040 0 SG103101102100SG =1 The f

Página 412 - Enable for I/O byte 0

Position Decoding IP 2407.4 An Example of Position Decoding: Heat TreatmentThe induction coil of an induction furnace for heat treatment must move a

Página 413 - IP 240 Operation

IP 240 Position DecodingFunctional descriptionAll data required for operation must be entered in a data block (DB 10 in the example). The datainclud

Página 414 - 5.2 Output Inhibit (BASP)

Position Decoding IP 240StipulationsInput card Module address 4Output card Module address 12Analog output card Module address 128 (1st output)IP 240

Página 415

IP 240 Position DecodingInputs, outputs, flags, timers and counters usedOPERAND SYMBOL COMMENTI 4.0 EMERG STOPI 4.1 START START RUNI 4.2 ON INTPNT

Página 416

Position Decoding IP 240DB10 LEN=38

Página 417

IP 240 Position DecodingDB12 LEN=73