Siemens Building Technologies
Cerberus Division
Alarm general information
cont.
Message order
Messages are presented in the following order:
1. unacknowledged alarms
2. acknowledged alarms
3. isolated alarms
Within these categories the messages are sorted chronologically.
Acknowledge
Ü Each message has to be acknowledged separately
1. Select the desired unacknowledged mes-
sage
2. Press
ACK
Ü The message state text changes
from NACK to ACKD
Ü The unacknowledged message is
placed on top
Supplementary information
The logical address of the alarming zone
(if programmed)
How can an intervention text be read out ?
1. Press «Alarms» key and select the de-
sired message by pressing
NEXT
or
PREV
, if necessary (the selected mes-
sage is displayed in inverted colors)
2. Press
ok
Ü The intervention text is displayed (if
programmed)
3. Pressing
ok
again returns back to the
original message
Reset
Ü Each message has to be reset separately
Ü Unacknowledged messages are reset in the same way as acknowledged ones
1. Select the message to be reset
2. Press
RESET
Ü The confirmation dialog is displayed
3. Press
ACK
to confirm
01 AUTOM. ALARM SMOKE NACK
logical address
of the alarming
zone
main building / 1st floor 01/001/004
room 104
02 AUTOM. ALARM HEAT NACK
main building / 1st floor 01/001/006
room 102
F1:function ok:interv.text F2:menu
Fire brigade REQUESTED Zones: 2
message state
NACK = not
acknowledged
message state
ACKD =
acknowledged
main building / 1st floor 01/001/006
room 104
02 AUTOM. ALARM SMOKE ACKD
main building / 1st floor 01/001/004
room 102
F1:function ok:interv.text F2:menu
Fire brigade REQUESTED Zones: 2
01 AUTOM. ALARM HEAT NACK
01 AUTOM. ALARM SMOKE ACKD
main building / 1st floor 01/001/004
room 104
Fire brigade REQUESTED Zones: 2
F1:function ok:interv.text F2:menu
DANGER: hazardeous materials !!
-> alert emergency squad
Fire brigade REQUESTED Zones: 2
intervention
text
main building / 1st floor 01/001/006
02 AUTOM. ALARM HEAT ACKD
room 102
ok:message
main building / 1st floor 01/001/004
room 104
02 AUTOM. ALARM HEAT ACKD
main building / 1st floor 01/001/006
room 102
F1:function ok:interv.text F2:menu
Fire brigade REQUESTED Zones: 2
01 AUTOM. ALARM SMOKE ACKD
PRESS ACKNOWLEDGE TO CONFIRM RESET
any other key:end