PrefaceixSIMATIC TIWAY I Series 500 NIM User ManualPrefaceThis manual contains the information necessary to install and operate theSeries 500 Networ

Página 3 - MANUAL PUBLICATION HISTORY

NIM Primitives4-47SIMATIC TIWAY I Series 500 NIM User ManualSymbol Value DefinitionXX Number of records in errorCC Record numbers in errorDD Data rec

Página 4 - LIST OF EFFECTIVE PAGES

NIM Primitives4-48SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Table 4-8 provides a state diagram for th

Página 5 - Contents

NIM Primitives4-49SIMATIC TIWAY I Series 500 NIM User ManualThe first request also contains the “between response to request” time-outvalue. This val

Página 6 - Chapter 4 NIM Primitives

NIM Primitives4-50SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Upload Response Parameter Descriptions. T

Página 7 - Contents v

NIM Primitives4-51SIMATIC TIWAY I Series 500 NIM User ManualThere are four primary forms of the upload primitive.• Initiate upload — places the attac

Página 8 - List of Figures

NIM Primitives4-52SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Upload Data Request and ResponseRequest:

Página 9 - List of Tables

NIM Primitives4-53SIMATIC TIWAY I Series 500 NIM User ManualIf the terminate upload command is issued and the attached device is not inthe upload mod

Página 10

NIM Primitives4-54SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Download Request Parameter DescriptionsTh

Página 11

NIM Primitives4-55SIMATIC TIWAY I Series 500 NIM User ManualDownload Response Parameter DescriptionsThe basic format of the response is as follows:LL

Página 12 - TIWAY I Overview

NIM Primitives4-56SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Like the program upload primitive, there

Página 13 - 1.1 TIWAY I System Overview

PrefacexSIMATIC TIWAY I Series 500 NIM User Manual• APPENDIX E — SPECIFICATIONS provides general specifications forthe Series 500 NIM.• APPENDIX F — P

Página 14

NIM Primitives4-57SIMATIC TIWAY I Series 500 NIM User ManualDownload Device Request and ResponseRequest: LLLL 59 01 RRRR YYYY WW ZZ DD ... DDResponse

Página 15

NIM Primitives4-58SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Download ExamplesThe following pages cont

Página 16

NIM Primitives4-59SIMATIC TIWAY I Series 500 NIM User ManualTable 4-8 Summary of PrimitivesPrimitive

Página 17

NIM Primitives4-60SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Table 4-8 Summary of Primitives (continue

Página 18

NIM Primitives4-61SIMATIC TIWAY I Series 500 NIM User ManualTable 4-8 Summary of Primitives (continued)  

Página 19 - Network Design Considerations

NIM Primitives4-62SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Table 4-9 Summary of Primitives (Extended

Página 20

NIM Primitives4-63SIMATIC TIWAY I Series 500 NIM User ManualTable 4-9 Summary of Primitives (Extended Addressing) (continued)

Página 21

NIM Primitives4-64SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Table 4-9 Summary of Primitives (Extended

Página 22

PM550 CIM RequirementsA-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix APM550 CIM RequirementsA.1 Introduction A-2. . . . . . . . . . . . . . .

Página 23

PM550 CIM RequirementsA-2SIMATIC TIWAY I Series 500 NIM User ManualA.1 IntroductionThis appendix discusses biasing and terminating the TIWAY I Local L

Página 24

TIWAY I Overview1-1SIMATIC TIWAY I Series 500 NIM User ManualChapter 1TIWAY I Overview1.1 TIWAY I System Overview 1-2. . . . . . . . . . . . . . . .

Página 25

PM550 CIM RequirementsA-3SIMATIC TIWAY I Series 500 NIM User ManualA.2 Local Line LengthThe PM550 CIM supports operation over the Local Line at dista

Página 26

PM550 CIM RequirementsA-4SIMATIC TIWAY I Series 500 NIM User ManualA.3 Local Line Bias and TerminationFor TIWAY I networks using the Local Line, some

Página 27

PM550 CIM RequirementsA-5SIMATIC TIWAY I Series 500 NIM User Manual2. If more than one CIM is attached to a Local Line, place CIMs at theextreme ends

Página 28

Floating Point NumbersB-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix BFloating Point NumbersB.1 Introduction B-2. . . . . . . . . . . . . . .

Página 29

Floating Point NumbersB-2SIMATIC TIWAY I Series 500 NIM User ManualB.1 IntroductionThe Series 500 NIM allows IBM excess 64 and IEEE representation of

Página 30

Floating Point NumbersB-3SIMATIC TIWAY I Series 500 NIM User ManualB.2 IBM FormatFloating point numbers are stored in memory in two 16-bit words asil

Página 31

Floating Point NumbersB-4SIMATIC TIWAY I Series 500 NIM User ManualIBM Format (continued)

Página 32

Floating Point NumbersB-5SIMATIC TIWAY I Series 500 NIM User ManualB.3 IEEE FormatThe exponent portion of the IEEE format is similar to the IBM forma

Página 33 - 2.4 Local Line Biasing

Floating Point NumbersB-6SIMATIC TIWAY I Series 500 NIM User ManualIEEE Format (continued)

Página 34

Network Configuration Data SheetC-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix CNetwork Configuration Data Sheet

Página 35

TIWAY I Overview1-2SIMATIC TIWAY I Series 500 NIM User Manual1.1 TIWAY I System OverviewTIWAY I is an industrial Local Area Network designed to satisf

Página 36 - Installation

Network Configuration Data SheetC-2SIMATIC TIWAY I Series 500 NIM User ManualDate Name or IdentifierDATA DEFINITION TABLEDataTypeStartingAddressNumber

Página 37 - 3.1 General Requirements

Network Evaluation FormD-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix DNetwork Evaluation FormIf you would like Siemens to evaluate your netwo

Página 38 - 3.2 Installing the NIM

Network Evaluation FormD-2SIMATIC TIWAY I Series 500 NIM User Manual

Página 39

SpecificationsE-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix ESpecificationsOperating temperature range 0 to 60 C (32 to 140 F)Storage

Página 40

Primitive ExamplesF-1SIMATIC TIWAY I Series 500 NIM User ManualAppendix FPrimitive ExamplesThe following TIWAY I Primitive example (which does not in

Página 41 - 3.4 Setting the Dipswitches

Primitive ExamplesF-2SIMATIC TIWAY I Series 500 NIM User ManualResponse: LLLL A0 HH DDDD DDDD = 000A A0 00 8464 8665 A001 01F4 LLLL (Length) = 000A Pr

Página 42

Customer ResponseWe would like to know what you think about our user manuals so that we can serve you better.How would you rate the quality of our man

Página 43

BUSINESS REPLY MAILFIRST CLASSPERMIT NO.3JOHNSON CITY, TNFOLDFOLDPOSTAGE WILL BE PAID BY ADDRESSEENO POSTAGENECESSARYIF MAILEDIN THEUNITED STATESATTN:

Página 44

                    

Página 45

TIWAY I Overview1-3SIMATIC TIWAY I Series 500 NIM User ManualTIWAY I network products provide a number of user-selectable options.• Baud rates are se

Página 46

TIWAY I Overview1-4SIMATIC TIWAY I Series 500 NIM User ManualTIWAY I System Overview (continued)

Página 47

TIWAY I Overview1-5SIMATIC TIWAY I Series 500 NIM User ManualTIWAY I provides a Universal Command Language for all communicationon the network. The U

Página 48

TIWAY I Overview1-6SIMATIC TIWAY I Series 500 NIM User ManualTIWAY I System Overview (continued)The Series 500 NIM provides several features which ens

Página 49 - 3.5 Series 500 NIM Self Tests

TIWAY I Overview1-7SIMATIC TIWAY I Series 500 NIM User ManualTable 1-1 provides a complete listing of the primitives and data typessupported in each

Página 50

Network Design Considerations2-1SIMATIC TIWAY I Series 500 NIM User ManualChapter 2Network Design Considerations2.1 TIWAY I Network Configuration 2-2

Página 51

!DANGERDANGER indicates an imminently hazardous situation that, if not avoided, willresult in death or serious injury.DANGER is limited to the most ex

Página 52 - 3.6 Module Login Verification

Network Design Considerations2-2SIMATIC TIWAY I Series 500 NIM User Manual2.1 TIWAY I Network ConfigurationTIWAY I is a multi-drop communication netwo

Página 53

Network Design Considerations2-3SIMATIC TIWAY I Series 500 NIM User ManualFigure 2-1 is a simplified block diagram of the Series 500 NIM. The media

Página 54

Network Design Considerations2-4SIMATIC TIWAY I Series 500 NIM User ManualTIWAY I Network Configuration (continued)The basic difference in the NIM mod

Página 55 - 4.1 TIWAY I Primitives

Network Design Considerations2-5SIMATIC TIWAY I Series 500 NIM User Manual2.2 RS-232-C Cable InstallationThe physical layer in TIWAY I provides a mod

Página 56 - 4.2 Primitive Functions

Network Design Considerations2-6SIMATIC TIWAY I Series 500 NIM User Manual2.3 Local Line Cable InstallationThe following paragraphs describe Local Lin

Página 57

Network Design Considerations2-7SIMATIC TIWAY I Series 500 NIM User ManualThe TIWAY I local line network cable consists of a main cable or spine with

Página 58

Network Design Considerations2-8SIMATIC TIWAY I Series 500 NIM User ManualFigure 2-2 Number of Local Line Secondaries Versus Cable Length

Página 59 - 

Network Design Considerations2-9SIMATIC TIWAY I Series 500 NIM User ManualLocal Line Cable Installation (continued)As shown in Figure 2-2, when you u

Página 60

Network Design Considerations2-10SIMATIC TIWAY I Series 500 NIM User ManualFigure 2-3 TIWAY I Tap HousingWith the cover removed from the PPX:500–5606

Página 61

Network Design Considerations2-11SIMATIC TIWAY I Series 500 NIM User ManualLocal Line Cable Installation (continued)Some major points to consider dur

Página 62 - 4.4 Primitive Logical Groups

MANUAL PUBLICATION HISTORYSIMATIC TIWAY I Series 500 NIM User ManualOrder Manual Number: PPX:TIWAY–8110Refer to this history in all correspondence a

Página 63

Network Design Considerations2-12SIMATIC TIWAY I Series 500 NIM User ManualFigure 2-4 Tap Spacing Examples

Página 64

Network Design Considerations2-13SIMATIC TIWAY I Series 500 NIM User ManualLocal Line Cable Installation (continued)Cable routing should be planned a

Página 65

Network Design Considerations2-14SIMATIC TIWAY I Series 500 NIM User ManualSurface Duct Routing. Surface ducting for network cabling is usuallyinstall

Página 66

Network Design Considerations2-15SIMATIC TIWAY I Series 500 NIM User Manual2.4 Local Line BiasingThe TIWAY I Local Line is designed to operate with s

Página 67 - 6x, 7x, and 8x = IEEE format

Network Design Considerations2-16SIMATIC TIWAY I Series 500 NIM User Manual

Página 68

Network Design Considerations2-17SIMATIC TIWAY I Series 500 NIM User ManualLocal Line Biasing (continued)Termination of the Local Line must be at the

Página 69

Installation3-1SIMATIC TIWAY I Series 500 NIM User ManualChapter 3Installation3.1 General Requirements 3-2. . . . . . . . . . . . . . . . . . . . . .

Página 70

Installation3-2SIMATIC TIWAY I Series 500 NIM User Manual3.1 General RequirementsThe following requirements must be met in order to install and use a

Página 71

Installation3-3SIMATIC TIWAY I Series 500 NIM User Manual3.2 Installing the NIMThis section describes how to mount the NIM in the Series 500 I/O base

Página 72

Installation3-4SIMATIC TIWAY I Series 500 NIM User Manual3.3 Inserting the Module into the BaseBefore using the module, you should decide whether you

Página 73

LIST OF EFFECTIVE PAGESPages Description Pages DescriptionCover/Copyright FifthHistory/Effective Pages Fifthiii — x Fifth1-1 — 1-7 Fifth2-1 — 2-16 Fi

Página 74

Installation3-5SIMATIC TIWAY I Series 500 NIM User ManualOnce the keys are in place, orient the module so that the indicators are onthe top half of t

Página 75

Installation3-6SIMATIC TIWAY I Series 500 NIM User Manual3.4 Setting the DipswitchesAs Figure 3-3 illustrates, there are two blocks of dipswitches on

Página 76

Installation3-7SIMATIC TIWAY I Series 500 NIM User ManualTable 3-2 Address Examples1 25 203SW8 Open Open OpenSW7 Closed Closed OpenSW6 Closed Closed

Página 77

Installation3-8SIMATIC TIWAY I Series 500 NIM User ManualSetting the Dipswitches (continued)

Página 78

Installation3-9SIMATIC TIWAY I Series 500 NIM User ManualConfiguration switches 1 through 4 (on the configuration switch bank)select the data transmi

Página 79

Installation3-10SIMATIC TIWAY I Series 500 NIM User ManualSetting the Dipswitches (continued)Synchronous/Asynchronous Selection. Configuration switch

Página 80

Installation3-11SIMATIC TIWAY I Series 500 NIM User ManualLockout/Enable. Configuration switch 9 enables the P/C to “lockout” theNIM during time-crit

Página 81

Installation3-12SIMATIC TIWAY I Series 500 NIM User ManualSetting the Dipswitches (continued)A successful completion of these tests will leave only th

Página 82

Installation3-13SIMATIC TIWAY I Series 500 NIM User ManualLocal/Remote. When set to remote, this two-position switch enables theNIM to perform write

Página 83

Installation3-14SIMATIC TIWAY I Series 500 NIM User Manual3.5 Series 500 NIM Self TestsThe three levels of Series 500 NIM self tests available in the

Página 84

Contents iiiContentsChapter 1 TIWAY I Overview1.1 TIWAY I System Overview 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 85

Installation3-15SIMATIC TIWAY I Series 500 NIM User ManualFailures detected in the ROM integrity test will cause the NIM GOOD LEDto extinguish, and f

Página 86 - 

Installation3-16SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Self Tests (continued)Start of execution of the User-Initiated Self-Test will

Página 87

Installation3-17SIMATIC TIWAY I Series 500 NIM User Manual3.6 Module Login VerificationAfter the NIM has been installed and configured, you should ve

Página 88

Installation3-18SIMATIC TIWAY I Series 500 NIM User Manual3.7 Connecting the Network CablesNetwork cabling should already be in place before NIM insta

Página 89

NIM Primitives4-1SIMATIC TIWAY I Series 500 NIM User ManualChapter 4NIM Primitives4.1 TIWAY I Primitives 4-2. . . . . . . . . . . . . . . . . . . . .

Página 90

NIM Primitives4-2SIMATIC TIWAY I Series 500 NIM User Manual4.1 TIWAY I PrimitivesPrimitives are high-level commands that allow a user to access like d

Página 91

NIM Primitives4-3SIMATIC TIWAY I Series 500 NIM User Manual4.2 Primitive FunctionsPrimitives serve as the command structure that a TIWAY I Primary us

Página 92

NIM Primitives4-4SIMATIC TIWAY I Series 500 NIM User Manual4.3 Primitive Structure and OperationA Primitive consists of multiple fields that specify t

Página 93

NIM Primitives4-5SIMATIC TIWAY I Series 500 NIM User ManualFigure 4-1 illustrates the basic Primitive structure when HDLC operation isselected. There

Página 94 - 

NIM Primitives4-6SIMATIC TIWAY I Series 500 NIM User ManualPrimitive Structure and Operation (continued)

Página 95

iv Contents3.5 Series 500 NIM Self Tests 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 96 - (repeated)

NIM Primitives4-7SIMATIC TIWAY I Series 500 NIM User ManualException when Reading. The device performing the Primitive operationaborts execution of a

Página 97

NIM Primitives4-8SIMATIC TIWAY I Series 500 NIM User ManualPrimitive Structure and Operation (continued)The upload and download formats will always be

Página 98

NIM Primitives4-9SIMATIC TIWAY I Series 500 NIM User Manual4.4 Primitive Logical GroupsAll Siemens TIWAY Primitives fall into logical groups accordin

Página 99

NIM Primitives4-10SIMATIC TIWAY I Series 500 NIM User ManualPrimitive Logical Groups (continued)The subset of TIWAY I Primitives supported by the Seri

Página 100

NIM Primitives4-11SIMATIC TIWAY I Series 500 NIM User Manual4.5 Primitive Field DefinitionsThe basic Primitive Request and Response field formats are

Página 101 - NIM Primitives

NIM Primitives4-12SIMATIC TIWAY I Series 500 NIM User ManualPrimitive Field Definitions (continued)The symbols used in the remainder of this section t

Página 102 - 

NIM Primitives4-13SIMATIC TIWAY I Series 500 NIM User ManualWithin the Descriptor Field (see Figure 4-3) are different fields to define thefollowing:

Página 103

NIM Primitives4-14SIMATIC TIWAY I Series 500 NIM User Manual4.6 Data Element Types and FormatsThe data element types (TTs) and their length (in bytes)

Página 104

NIM Primitives4-15SIMATIC TIWAY I Series 500 NIM User ManualTable 4-4 Basic Data Unit Format (continued)TT Data Element TypeLength(in bytes)** 26 or

Página 105

NIM Primitives4-16SIMATIC TIWAY I Series 500 NIM User ManualData Element Types and Formats (continued)Table 4-4 Basic Data Unit Format (continued)TT D

Página 106

Contents vWrite Block Primitive – Code 30 4-39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wri

Página 107

NIM Primitives4-17SIMATIC TIWAY I Series 500 NIM User Manual

Página 108

NIM Primitives4-18SIMATIC TIWAY I Series 500 NIM User ManualData Element Types and Formats (continued)

Página 109

NIM Primitives4-19SIMATIC TIWAY I Series 500 NIM User Manual     

Página 110

NIM Primitives4-20SIMATIC TIWAY I Series 500 NIM User ManualData Element Types and Formats (continued)

Página 111 - Primitives

NIM Primitives4-21SIMATIC TIWAY I Series 500 NIM User Manual 

Página 112

NIM Primitives4-22SIMATIC TIWAY I Series 500 NIM User ManualData Element Types and Formats (continued)

Página 113

NIM Primitives4-23SIMATIC TIWAY I Series 500 NIM User Manual   

Página 114

NIM Primitives4-24SIMATIC TIWAY I Series 500 NIM User Manual4.7 Data Element Address RangesThe maximum data element locations (AAAA field) for each da

Página 115

NIM Primitives4-25SIMATIC TIWAY I Series 500 NIM User ManualTable 4-5 Data Element Address RangesP/C TypeData Type520–1101530–1102530–1104530–1108520

Página 116

NIM Primitives4-26SIMATIC TIWAY I Series 500 NIM User Manual4.8 Data Field Length RestrictionsTable 4-6 and Table 4-7 delineate the maximum length of

Página 117

vi ContentsList of Figures1-1 TIWAY I System Block Diagram 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 118 - PM550 CIM Requirements

NIM Primitives4-27SIMATIC TIWAY I Series 500 NIM User ManualTable 4-7 Maximum Write Primitive Byte Length

Página 119 - A.1 Introduction

NIM Primitives4-28SIMATIC TIWAY I Series 500 NIM User Manual4.9 Series 500 NIM Primitive DescriptionsThe following paragraphs describe the NIM Primiti

Página 120 - A.2 Local Line Length

NIM Primitives4-29SIMATIC TIWAY I Series 500 NIM User ManualSymbol Value DefinitionDDDD16 TT not programmed in attached device.17 The attached device

Página 121

NIM Primitives4-30SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 1.1, 2.1, 2.2 and

Página 122

NIM Primitives4-31SIMATIC TIWAY I Series 500 NIM User ManualAvailability: Releases 1.1, 2.1, 2.2, and 3.0Primitive 02 is the machine status Primitive

Página 123 - Floating Point Numbers

NIM Primitives4-32SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 1.1, 2.1, 2.2, and

Página 124 - B.1 Introduction

NIM Primitives4-33SIMATIC TIWAY I Series 500 NIM User ManualAvailability: Releases 1.1, and 2.1, 2.2, and 3.0Primitive 04 is the format Primitive tha

Página 125 - B.2 IBM Format

NIM Primitives4-34SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 2.1, 2.2, and 3.0P

Página 126 - 

NIM Primitives4-35SIMATIC TIWAY I Series 500 NIM User ManualAvailability: Release 3.0Primitive 07, used with the Program Upload and Download Primitiv

Página 127 - B.3 IEEE Format

NIM Primitives4-36SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 1.1, 2.1, 2.2, and

Página 128 - IEEE Format (continued)

Contents viiList of Tables1-1 Primitive Support in NIM Software Releases 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 129 - Appendix C

NIM Primitives4-37SIMATIC TIWAY I Series 500 NIM User ManualAvailability: Releases 1.1, 2.1, 2.2, and 3.0Primitive 20 is a command to read a single c

Página 130 - DATA DEFINITION TABLE

NIM Primitives4-38SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 2.1, 2.2, and 3.0P

Página 131 - Network Evaluation Form

NIM Primitives4-39SIMATIC TIWAY I Series 500 NIM User ManualAvailability: Releases 1.1, 2.1, 2.2, and 3.0Primitive 30 is the Write Block Primitive, w

Página 132

NIM Primitives4-40SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Symbol Value DefinitionHH Attached device

Página 133 - Specifications

NIM Primitives4-41SIMATIC TIWAY I Series 500 NIM User ManualSymbol Value DefinitionCC Block number (1–20 hex)TT Data element typeNNNN Number of locat

Página 134 - Primitive Examples

NIM Primitives4-42SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Symbol Value DefinitionHH Attached device

Página 135

NIM Primitives4-43SIMATIC TIWAY I Series 500 NIM User ManualSymbol Value DefinitionTT Data element typeAAAA Data element locationDD DataResponse: LLL

Página 136 - Customer Response

NIM Primitives4-44SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Availability: Releases 2.1, 2.2, and 3.0T

Página 137 - JOHNSON CITY, TN

NIM Primitives4-45SIMATIC TIWAY I Series 500 NIM User ManualThe total byte count of data elements defined by the record(s) must notcause the Gather R

Página 138

NIM Primitives4-46SIMATIC TIWAY I Series 500 NIM User ManualSeries 500 NIM Primitive Descriptions (continued)Write and Gather Record Primitive – Code