Network Topologies
3.3 Ring Topology
SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
Operating Instructions, 01/2013, C79000-G8976-C270-03
11
Note:
Unused optical channels you intend to use later to expand the network cause a broken fiber-
optic cable signal if the monitoring is active. You can avoid this error message by setting
unused channels to the mode bus without fiber-optic link monitoring”. Remember that the
optical channels that are not connected must be protected against external light and pollution
by protective caps.
3.3 Ring Topology
3.3.1 Redundant Optical Ring
Figure 3-3 Network structure with a redundant optical ring topology
* If OLM / P22 or OLM / G22 are used, an additional DTE or bus segment
can be connected to Ch 0.
This network topology is a special form of the bus topology. “Closing the optical bus
achieves high operational reliability in the network. A redundant optical ring can only be
implemented using modules with two optical channels.
Monitoring mechanisms:
Send echo: yes
Monitor echo: yes
Suppress echo: yes
Segmentation: yes
The interruption of one or both fiber-optic cables between the modules is detected by the
OLM and the ring becomes an optical bus.