3 Installation and Commissioning
B23
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
3.4 Controlling the operating mode
You have the option of changing the mode of the CP between RUN and STOP
using the STEP 7 / NCM S7 configuration software (PLC > Accessible Nodes).
Procedure
S Switch from STOP to RUN:
The CP reads the configured and/or downloaded data into the work memory
and then changes to the RUN mode.
S Switch from RUN to STOP:
The CP changes to STOP. Established connections (ISO transport,
ISO-on-TCP, TCP, UDP connections) are terminated (transitional phase with
LED display “STOPPING”);
The reaction is as follows in STOP:
The communications connections mentioned above are terminated;
The configuration and diagnostics of the CP is possible (system connections
for configuration, diagnostics, and PG channel routing are retained);
HTTP access is possible
The routing function is active
The time of day is not forwarded
PROFINET IO is disabled.
PROFINET CBA is disabled.
Module access protection
The configurable module access protection has the following effects on the
functions described here:
S Module access protection is locked
The functions can be executed.
S Module access protection: Status dependent
With this setting, it is only possible to access the CP when the CPU is in STOP
mode.