Appendix E: Device Data Format
78 Siemens Energy & Automation, Inc.
Control Parameters 18 Bit Contents
7 Ground Fault Enable
6 Service Factor (0 = 1.0)
5Auto Reset Enable
4 Phase Unbalance Enable
3 Emergency Reset Enable
2 Jam Protection Enable
1 Loss of Load Enable
0 Reserved
Ambient Temperature 19 0...70 Degrees C
Reserved 20
23 For Future Expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
Device Command Data Retrieved From PLC (SAMMS LV and MV)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Change Timing Byte 1 New value for timing byte 1 (0
200 seconds)
2 = Change Timing Byte 2 New value for timing byte 2 (0
200 seconds)
3 = Force Pushbutton On Pushbutton to force on
1 = Stop/Off Button
2 = Start/On Button
3 = Left/Reverse Button
4 = Hand Button
5 = Off Button
6 = Auto Button
7 = Reserved for Later Use
8 = Reset after Trip
4 = Change Overload Trip Overload Trip Class (2–23)
5 = Change Ground Fault (0 = Warning, 1 = Protection Enabled)
6 = Change Phase Unbalance (0 = Protection Disabled, 1 = Enabled)
7 = Change Ambient Temperature Ambient Temperature (0–70)
Real-Time Device Data Stored in PLC (SAMMS LV and MV) (Continued)
Real-Time Data Register Location in
PLC Block
1
Range or Contents