Siemens DataNET Hub (DNH) Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Redes Siemens DataNET Hub (DNH). Siemens DataNET Hub (DNH) User's Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 0
December 2001 User’s Manual
2000585-001
Siemens Applied Automation
Siemens Applied AutomationSiemens Applied Automation
Siemens Applied Automation
Advance DataNET
Hub (DNH)
Vista de página 0
1 2 3 4 5 6 ... 96 97

Resumo do Conteúdo

Página 1 - Hub (DNH)

December 2001 User’s Manual 2000585-001 Siemens Applied AutomationSiemens Applied AutomationSiemens Applied AutomationSiemens Applied Automation

Página 2 - Copyright Notice

2 •••• Introduction 2000585-001 Overview, Continued The Advance DataNET Hub (DNH) is available in three package configu-rations: • 19-inch Rack U

Página 3 - Table of Contents

2000585-001 Introduction •••• 3 Overview, Continued A network of DataNET hubs forms a tree-like hierarchy. A DNH may connect to as many as eight “

Página 4 - Table of Contents, Continued

4 •••• Introduction 2000585-001 DataNET Hub Operation Figure 1-4 shows the individual links that connect three DataNET hubs and several end devices

Página 5 - Preface

2000585-001 Introduction •••• 5 DataNET Hub Operation, Continued DataNET switching operates by dynamically and automatically learning the topology

Página 6 - Technical Support

6 •••• Introduction 2000585-001 DataNET Hub Specifications Dimensions Rack Mounted Package Configuration See Figure 1-5 for Outline Drawing and

Página 7

2000585-001 Introduction •••• 7 DataNET Hub Specifications, Continued Ambient Installation Conditions Operation: -18° to +50°C (0° to 122°F) 0-99%

Página 8

8 •••• Introduction 2000585-001 DataNET Hub Specifications, Continued DataNET Option, Standard Cable • Cable connection by Belden 9182 (single p

Página 9 - I/O Ports

2000585-001 Introduction •••• 9 DataNET Hub Specifications, Continued The Table below compares key communication features between using Advance Da

Página 10 - Overview, Continued

10 • Introduction 2000585-001 DataNET Hub Specifications, Continued Figure 1-3 Description U.S. Inches Metric mm A Rack Height 6.97 177

Página 11

2000585-001 Introduction • 11 DataNET Hub Specifications, Continued Figure 1-4 Description U.S. Inches Metric mm A Wall Width 17.48 444 B W

Página 12 - DataNET Hub Operation

Copyright Notice  2000 by Siemens Applied Automation Bartlesville, Oklahoma, 74003, U.S.A. All rights reserved. This publication is for information o

Página 13 - Transparenc

12 •••• Introduction 2000585-001 DataNET Hub Specifications, Continued PKLMNOc/lSTTOPK0Pc/lRBOTTOMCQLEFTGHIJc/lQRIGHTDAEFFRONTB Figure 1-7 Des

Página 14 - DataNET Hub Specifications

2000585-001 Introduction •••• 13 DataNET Hub Specifications, Continued L Spacing from wall to front cable entry hole (top and bottom) 127 5 M

Página 16

2000585-001 Installation •••• 15 Chapter 2 Installation Overview This chapter is intended for installation personnel. After completing the procedur

Página 17 - Communication

16 •••• Installation 2000585-001 Unpacking and Inspection This section provides the steps to follow when receiving and unpacking the Advance DataNE

Página 18

2000585-001 Installation •••• 17 Wall or Rack Mounting Installation The Advance DataNET Hub should be: • Installed in a location that is free from

Página 19

18 •••• Installation 2000585-001 Wall or Rack Mounting Installation, Continued The DNH rack mount configuration is designed for a standard 19-inch

Página 20

2000585-001 Installation •••• 19 Site Wiring Requirements How you wire to the DNH is dependent upon the site requirements: • CE (Conformite Europe

Página 21

20 •••• Installation 2000585-001 Site Wiring Requirements, Continued The DataNET channel connections can be either copper wire or fiber optic cabl

Página 22

2000585-001 Installation •••• 21 Site Wiring Requirements, Continued The following information pertains when using copper wire See Page 23, CE Ins

Página 23 - Chapter 2

2000585-001 Table of Contents • i Table of Contents Preface iii Technical Support iv Safety Practices and Precautions v Introduction 1 Overview

Página 24 - Unpacking and Inspection

22 •••• Installation 2000585-001 Site Wiring Requirements, Continued Use Cable Gland wiring method. Each cable gland allows entry of one duplex fi

Página 25 - PROTECTION

2000585-001 Installation •••• 23 CE Installations This section should be used for installation sites that must conform to CE (Conformite Europeene)

Página 26 - Wiring Requirements

24 •••• Installation 2000585-001 CE Installations, Continued 3. A split ferrite filter must be clamped to DataNET copper wire and fixed immediate

Página 27 - Site Wiring Requirements

2000585-001 Installation •••• 25 Wiring Connections Two removable access plates provide power and I/O entry through the underside of the DNH. The p

Página 28 - DataNET Channels

26 •••• Installation 2000585-001 AC Power (Mains) Connections Each of the DNH electronic modules has a Power Supply Assembly lo-cated below the Dat

Página 29 - Cable Connections

2000585-001 Installation •••• 27 AC Power (Mains) Connections, Continued Step Action 3. Install 15-Ampere circuit breakers, disconnect switches

Página 30 - Ethernet Communica

28 •••• Installation 2000585-001 AC Power (Mains) Connections, Continued Step Action 7. Plug the connector back into its base and secure the tw

Página 31

2000585-001 Installation •••• 29 DataNET Copper Connections The DNH consist of two identical hubs in one enclosure. The left side is usually the Da

Página 32 - CE Installations, Continued

30 •••• Installation 2000585-001 DataNET Copper Connections, Continued See Figure 2-1. Each DataNET Hub board has nine DataNET ports. One of the D

Página 33 - Wiring Connections

2000585-001 Installation •••• 31 DataNET Copper Connections, Continued Behind each single port connector is an associated jumper pin block, see Fi

Página 34 - AC Power (Mains) Connections

ii •••• Table of Contents 2000585-001 Table of Contents, Continued Command Summary 69 Command Descriptions 69 Parts Catalog 85 Introduction 85

Página 35

32 •••• Installation 2000585-001 DataNET Copper Connections, Continued Step Action 1. Plug the DataNET Hub Signal Equalizer Board into the se-l

Página 36

2000585-001 Installation •••• 33 DataNET Copper Connections, Continued Each of the four downlink connectors (TB15, TB16, TB17, TB18) contain wring

Página 37 - DataNET Copper Connections

34 •••• Installation 2000585-001 DataNET Hub Signal Equalizer Board This section sets the switches on the DataNET Hub Signal Equalizer board. This

Página 38 - CONNECTORS

2000585-001 Installation •••• 35 DataNET Hub Signal Equalizer Board, Continued When cable lengths are unknown, or the cable is other than the rec

Página 39 - 2000585-001 Installation •

36 •••• Installation 2000585-001 DataNET Hub Signal Equalizer Board, Continued Selec-tion Ratio DB loss SW1 SW2 SW3 1 2 3 1 2 3 1 2

Página 40

2000585-001 Installation •••• 37 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths This section is used to set the swi

Página 41 - TB15 – TB18

38 •••• Installation 2000585-001 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Signals are viewed with a

Página 42 - Recommended Cable

2000585-001 Installation •••• 39 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued This procedure is for de

Página 43 - 2000585-001 Installation •

40 •••• Installation 2000585-001 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Step Action 3. Examine

Página 44 - Sample Calculations

2000585-001 Installation •••• 41 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Step Action 3. cont. The

Página 45 - Cable Lengths

2000585-001 Preface •••• iii Preface This manual is intended to introduce users to the Advance DataNET Hub (DNH). It includes complete instruction

Página 46

42 •••• Installation 2000585-001 DataNET Fiber Optic Connections All DataNET Fiber Optic uplink and downlink port connections are made through the

Página 47

2000585-001 Installation •••• 43 DataNET Fiber Optic Connections Duplex Fiber, 62.5/125 micron 1. Plug the DataNET Fiber Optic Coupler board in

Página 49

2000585-001 Installation •••• 45 Ethernet Connections The DNH consists of two identical hub modules in one enclosure. The left side is usually th

Página 50 - • Installation 2000585-001

46 •••• Installation 2000585-001 Ethernet Connections, Continued 1. The 10BASET data cable requires a minimum of two twisted pairs (transmit pair

Página 51 - CONNECTOR

2000585-001 Data Communications Setup •••• 47 Chapter 3 Data Communications Setup Introduction This chapter provides maintenance personnel instruc

Página 52

48 •••• Data Communications Setup 2000585-001 Introduction, Continued This chapter provides the following information: Topic Page Configuring Your

Página 53 - Ethernet Connections

2000585-001 Data Communications Setup •••• 49 Configuring Your PC The Advance DataNET Hub (DNH) has a built-in utility for configuring its operati

Página 54 - 10BASE-T Cable

58 • Data Communications Setup 2000585-001 Setting Network Address, Continued See Assigning an IP Address, page 59 to learn how to assign an IP Ad

Página 55 - Chapter 3

2000585-001 Data Communications Setup •••• 51 Configuring Your PC, Continued 8. Scroll each field and select the following Port Settings: Bits p

Página 56 - Introduction, Continued

iv •••• Preface 2000585-001 Technical Support At Siemens Applied Automation we take pride in the on going support we provide our customers. When yo

Página 57 - Configuring Your PC

52 •••• Data Communications Setup 2000585-001 Configuring Your PC, Continued 13. Click Terminal Settings button. The Terminal Settings dialog box

Página 58

2000585-001 Data Communications Setup •••• 53 Configuring Your PC, Continued 16. Click OK to return to main menu. 17. From the Main menu select

Página 59

54 •••• Data Communications Setup 2000585-001 Establishing a Connection Once your PC is set up, as described in Configuring Your PC, you are ready

Página 60

2000585-001 Data Communications Setup •••• 55 Establishing a Connection, Continued A password name can consist of any combination of alphanumeric

Página 61

56 •••• Data Communications Setup 2000585-001 Establishing a Connection, Continued 3. At the >>>> prompt type: login password and pres

Página 62 - Establishing a Connection

2000585-001 Data Communications Setup •••• 57 Setting Network Address This section provides instructions to configure an Advance DataNET ‘A’ or ‘

Página 63 - How to Log On

58 • Data Communications Setup 2000585-001 Setting Network Address, Continued See Assigning an IP Address, page 59 to learn how to assign an IP Ad

Página 64 - Remote Connection

2000585-001 Data Communications Setup •••• 59 Assigning an IP Address Each individual hub board (“hub-half”) in the system must have a unique IP

Página 65 - Setting Network Address

60 •••• Data Communications Setup 2000585-001 Firmware Updates Periodically we will provide our users with firmware upgrades. Perform the following

Página 66

2000585-001 Data Communications Setup • 61 Firmware Updates, Continued 6. Click on Send Text File. The Send Text File dialog box will appear. In

Página 67 - Assigning an IP Address

2000585-001 Safety Practices and Precautions •••• v Safety Practices and Precautions This product has been designed and tested in accordance with

Página 68 - Firmware Updates

62 •••• Data Communications Setup 2000585-001 System Status LEDs The Advance DataNET Hub Communication boards have status LEDs for monitoring the D

Página 69 - Firmware Updates, Continued

2000585-001 Data Communications Setup •••• 63 System Status LEDs, Continued The yellow (WARN) blink codes are shown below. The yellow (WARN) stat

Página 70 - System Status LEDs

64 • Data Communications Setup 2000585-001 System Status LEDs, Continued There are four Ethernet Link Status LEDs. Link Active LED is Green (on

Página 71 - Hub Port LEDs

2000585-001 Data Communications Setup •••• 65 Troubleshooting This chapter is intended for maintenance personnel. Failure of the DNH to establish

Página 72 - Cross Link Status

66 •••• Data Communications Setup 2000585-001 Troubleshooting, Continued The device may have an invalid or duplicate device ID, IP address, Sub-ne

Página 73 - Troubleshooting

2000585-001 Data Communications Setup •••• 67 Troubleshooting, Continued If a DNH port green LED is off, or intermittently flashes between green

Página 74 - Troubleshooting, Continued

68 •••• Data Communications Setup 2000585-001 Troubleshooting, Continued 12. At the >>>> prompt type: test off Test off places the se

Página 75

2000585-001 Command Summary •••• 69 Chapter 4 Command Summary Command Descriptions This chapter is intended for maintenance personnel. This chapte

Página 76

70 •••• Command Summary 2000585-001 Command Descriptions, Continued list nnn, xxx List xxx events, starting with number nnn list on Continuously

Página 77 - Chapter 4

2000585-001 Command Summary •••• 71 Command Descriptions, Continued This command configures the hub-half IP address. Each individual hub board (“

Página 78

vi •••• Safety Practices and Precautions 2000585-001 Safety Practices and Precautions, Continued Before switching on the power, check that the ope

Página 79

72 •••• Command Summary 2000585-001 Command Descriptions, Continued This command sets the address of the IP router to which the hub-half should se

Página 80

2000585-001 Command Summary •••• 73 Command Descriptions, Continued This command deletes selected items from the hub’s Source Address Table (SAT)

Página 81 - “display” Command

74 •••• Command Summary 2000585-001 Command Descriptions, Continued This command displays the hub-half’s link state table. The link state table in

Página 82 - “download”

2000585-001 Command Summary •••• 75 Command Descriptions, Continued 5. After you have selected the “hub_rom.mot” file and click on “OK,” HyperTe

Página 83 - “dn” Command

76 •••• Command Summary 2000585-001 Command Descriptions, Continued dn window Displays the transmit “window” for the HDLC protocol used by DataNET

Página 84

2000585-001 Command Summary •••• 77 Command Descriptions, Continued dn portdelay timeSets the “port delay” parameter to the value given, in milli

Página 85

78 •••• Command Summary 2000585-001 Command Description, Continued This command generates a simple list of available commands. Enter the list com

Página 86 - “list” Command

2000585-001 Command Summary •••• 79 Command Description, Continued The event display gives a time-stamp, and an event description. All events oth

Página 87 - “login” Command

80 •••• Command Summary 2000585-001 Command Descriptions, Continued This command logs the user out of a session. The user must be logged out of th

Página 88 - “port” Command

2000585-001 Command Summary •••• 81 Command Descriptions, Continued This command places a selected port into a hardware diagnostic mode. The comm

Página 89 - “timeout” Command

2000585-001 Introduction •••• 1 Chapter 1 Introduction Overview The Advance DataNET Hub (DNH) functions as a communication router on an Advance Com

Página 90 - “trace” Command

82 •••• Command Summary 2000585-001 Command Descriptions, Continued The trace command controls the hub’s frame tracing function. This fea-ture cap

Página 91 - “validation timeout”

2000585-001 Command Summary •••• 83 Command Descriptions, Continued sets up tracing on downstream port 2, for input data only. trace crosslink ou

Página 92 - “verbose” Command

84 •••• Command Summary 2000585-001 Command Descriptions, Continued This command controls the event buffer display’s “verbose” mode. When verbose

Página 93 - Chapter 5

2000585-001 Parts Catalog •••• 85 Chapter 5 Parts Catalog Introduction This chapter is intended for maintenance personnel. The Chapter provides a

Página 94 - Available Parts

86 •••• Parts Catalog 2000585-001 Available Parts The available DNH assemblies and parts, with their applicable part num-ber are shown below. Part

Página 95 - Available Parts, Continued

2000585-001 Parts Catalog •••• 87 Available Parts, Continued Part Description Ordering Number Cable, fiber optic patch, 3 meter, MM 62.5/125; 2

Página 97 - Siemens Applied Automation

Siemens Applied Automation 500 West Highway 60, Bartlesville, OK 74003 Phone 918-662-7000, Fax 918-662-7052

Comentários a estes Manuais

Sem comentários