Application description
Connecting CU230P-2 DP to the PROFIBUS DP network
Commissioning of the Control Unit CU230P-2 DP with PROFIBUS ID-No: 35934076
Version 1 Issue May 2009 9/33
Copyright © Siemens AG 2009 All rights reserved
PDF_Commissioning_of_CU230P_2_DP_with Profibus_en_V1.doc
2.2 PROFIBUS DP cable connector and permitted cable lengths
PROFIBUS DP cable connector
For connecting the SINAMICS G120 frequency inverter, we recommend the
following
PROFIBUS DP cable connectors:
6GK1 500-0FC00
6GK1 500-0EA02
They are equipped with a switch through which the bus terminating resistor
can be connected.
Permissible cable lengths
The permissible cable lengths depend on the baud rate and the PROFIBUS
cable.
For more information, visit:
(http://www.automation.siemens.com/net/html_76/support/printkatalog.htm
)
2.3 General specifications and requirements for fault-free
communication
You can integrate up to 126 stations into a PROFIBUS DP network. These
must be subdivided into segments of up to 32 stations. You must activate
the bus terminating resistor for the first and last stations of each segment.
You can disconnect one or more slaves from the bus (by unplugging the
bus connector) without interrupting the communication for the other
stations. It is important to ensure that a bus terminating resistor is
connected to the "first" and "last" nodes.
Note
Communication with the controller, even when the line voltage is
switched off
You will have to supply the Control Unit with 24 V DC on terminals 31 and
32 if you require communication to take place with the controller when the
line voltage is switched off.