RuggedMC™ RMC30Installation GuideRuggedCom Inc.300 Applewood Crescent,Concord, OntarioCanada L4K 5C7 Web: http://www.ruggedcom.com/Tel: +1 905 856 52
2.3 Power Supply Wiring and GroundingDrawing 5 - RuggedMCTM Power Supply InputsThe RuggedMCTM power supply inputs are identical and are connected as f
2.4 Serial Ports – Signal DescriptionThe RMC30 is equipped with a seven-terminal phoenix style connector. This connector can accommodate one RS232 co
2.4.1 RS232 Data PortThe RMC30 is equipped with a single EIA/TIA RS232 compliant port, consisting of three terminals: Transmit, Receive, and Common.
2.4.2 RS422 and RS485 Data PortsThe RMC30 is equipped with a single RS485 / RS422 data port. In half duplex mode (See section 2.5 for RMC30 configura
Drawing 8 - Conceptual RS485 wiring diagramRuggedCom® 14 RuggedMC™ RMC30 Installation Guide Rev 105
2.5 RMC30 Quick Start RecommendationsThe following is an excerpt from the RMC30 User's Guide. It is included to aid those users experienced with
3 Technical Specifications3.1 Power Supply SpecificationsPower Supply Type Minimum InputMaximum InputInternalFuseRatingMaximum Power Consumption24 VD
3.2 Mechanical SpecificationsDrawing 9 - RMC30 Mechanical DimensionsParameter Value CommentsDimensions4.30 x 2.40 x 3.30 inches(110) x (61) x (84)
3.3 Operating EnvironmentParameter Range CommentsAmbient Operating Temperature-40 to 85°CAmbient Temperature as measured from a 30cm radius surroundin
4 Type Test Specifications4.1 IEC 61850-3 Type TestsIEC 61850-3 EMI TYPE TESTSTest Description Test Levels Severity LevelsIEC 61000-4-2 ESD Enclosure
CopyrightCOPYRIGHT © 2010 RuggedCom Inc. ALL RIGHTS RESERVEDDissemination or reproduction of this document, or evaluation and communication of its co
D.C. Power ports 30V Continuous, 300V for 1s4IEC 61000-4-17 Ripple on D.C. Power SupplyD.C. Power ports 10% 3IEC 60255-5 Dielectric Strength Signal po
4.3 IEC Environmental Type TestsENVIRONMENTAL TYPE TESTSTest Description Test Levels Severity LevelsIEC 60068-2-1 Cold Temperature Test Ad -40°C, 16
5 Agency ApprovalsAgency Standards CommentsCSA, CE CSA C22.2 No. 60950, UL 60950, EN 60950EN 61000-6-2ApprovedFCC FCC Part 15, Class AApprovedCISPR EN
Federal Communications Commission Radio Frequency Interference StatementThis equipment has been tested and found to comply with the limits for a Class
Table of Contents1 Product Overview...
1 Product OverviewINTRODUCTIONThe RuggedServer™ RMC30 is an industrially hardened, 2-port serial device server that has been specifically designed to
1.1 RMC30 Front Panel DescriptionThe RMC30 LED definitions are as follows:LED Activity DescriptionPower Solid (Green) Power OnAlarm Solid (Red) Alarm
1.2 RMC30 Side and Bottom ViewDrawing 2- RMC30 Side and Bottom ViewRuggedCom® 7 RuggedMC™ RMC30 Installation Guide Rev 105
2 Installation2.1 DIN Rail MountingDrawing 3 - RMC30 DIN Rail MountingRuggedCom® 8 RuggedMC™ RMC30 Installation Guide Rev 105
2.2 Panel MountingWith the use of an optional panel-mount adapter, the RuggedMCTM series of media converters can be panel mounted. Drawing 4 shows an
Comentários a estes Manuais