Mounting and Removing S800 I/O Units Section 2 Installation
20 3BSE056248
When disconnecting units from each other, use a screw driver according to Figure 7
Mounting and Removing S800 I/O Units
The S800 I/O is mounted on a standard DIN-rail according to EN 50022 NS35/7,5.
The DIN-rail is mounted in a cabinet or on an enclosure wall to a metal sheet with
fastening screws every 100 mm to ensure a good chassis ground connection in the
cabinet or an open rack. The ModuleBus master, ModuleBus Modem, MTUs and
S800L I/O modules are mounted to the DIN rail. In environments with major
vibrations, the MTUs shall also be screwed on the metal sheet. The FCI, ModuleBus
Modem and MTUs have a snap locking device that attaches it to the mounting rail.
It is possible to mount the FCI, ModuleBus Modem, MTUs and S800L I/O modules
both vertically and horizontally.
Figure 7. Separating the Base Plates
F
R
Rx/Tx
RTS
F
R
Rx1
Tx1
Rx2
Tx2
CI853
COM1 COM2
F
R
P
INIT
B
PM860
CN1
CN2
COM3
COM4
CI851