60CTS CT Supervision
The relay monitors each phase current input and operates
if any one or two inputs fall below the setting. The
element types have user operate and delay settings.
64H Restricted Earth Fault
The measured earth fault input may be used in a 64H
high impedance restricted earth fault scheme to provide
sensitive high speed unit protection. A calculation is
required to determine the values of the external series
stabilising resistor and non-linear shunt resistor which
can be ordered separately.
74T/CCS Trip & Close Circuit Supervision
The trip or close circuit(s) can be monitored via binary
inputs. Trip circuit failure raises an HMI alarm and
output(s).
Programmable Logic
The user can map binary inputs, protection elements,
LEDs and binary outputs together in a logical scheme.
Up to 4 logic equations can be defined using standard
logic functions e.g. Timers, AND/OR gates, Inverters and
Counters to provide the user required functionality.
Each logic equation output can be used for alarm &
indication and/or tripping.
Virtual Inputs/Outputs
There are 8 virtual inputs/outputs to provide internal
logical states to assist in the application of the functions.
Each virtual I/O can be assigned in the same way as a
physical I/O.
Circuit Breaker Maintenance
Two circuit breaker operations counters are provided to
assist with maintenance scheduling. The maintenance
counter records the overall number of operations and the
delta counter records the number of operations since the
last reset.
An I
2
t summation counter provides a measure of the
contact wear indicating the total energy interrupted by
the circuit breaker contacts.
Each counter has a user set target operations count
which, when reached, can be mapped to raise alarms/
binary outputs.
Sequence of event records
Up to 1000 events are stored and time tagged to 1ms
resolution.
Fault Records
The last 10 fault records are displayed on the relay fascia
and are also available through the communication
interface, with time and date of trip, measured quantities
and type of fault.
Waveform recorder
The waveform recorder stores analogue data for all poles
and the states of protection functions, binary inputs, LEDs
and binary outputs with user settable pre & post trigger
data. A record can be triggered from protection function,
binary input or via data communications. 10 records of 1
second duration are stored.
Real Time Clock
The time and date can be set and are maintained while
the relay is de-energised by a back up storage capacitor.
The time can be synchronized from a binary input pulse
or the data communication channel.
Serial Communications
The relay offers a USB serial port as standard on the front
of all units. All of the relays functions can be set on a PC
using Reydisp Evolution via the USB port. The connection
is made with a USB cable and operates with a ‘plug and
play’ connection, so no pre-setting of the relay is
required.
The front port can be switched off or set to use either the
DNP3.0, MODBUS-RTU, IEC60870-5-103 and ASCII
protocols for testing purposes.
A rear RS485 electrical connection is available on all units
for system interface connections. An internal terminating
resistor is provided, which can be connected into the
circuit by adding a wire loop between the relevant
terminals.
Fig 4. Typical RS485 connection
The rear RS485 can be user selected to be OFF, IEC60870-
5-103, MODBUS RTU or DNP3.0 protocol.
Data Acquisition -
Via Communication Interface
Siemens Protection Devices Limited 5