ANCB/DN Specifications, Continued
Cable Types
The following Table should be used when evaluating or selecting cable
for an existing or new installation.
Cable Type Vendors & P/N Installation Notes
Fiber Optic
MM 62.5/125; 2 Fiber Conductors
SEA P/N 1270002-002
Industry Available from
Multiple Vendors
New Installation as an
alternative to copper cable
Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)
2- Conductor Copper Wire SEA P/N 1686002-001
Belden P/N 9182
For
Belden Armored Cable
Order
SEA P/N 1680000-002
Recommended for Single
Channel
Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)
4-Conductor Copper Wire SEA P/N 1681000-003
Belden P/N SSD1743
Recommended for Dual
Channel
Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)
Ethernet Cat 5 Unshielded Twisted
pair (UTP)
SEA P/N 1681003-006
Industry Available from
Multiple Vendors
Recommended for short
distances or within shelters.
Max distance from analyzer
to hub or between hubs 600
meters (2000 ft)
4 Installation 2000592-001