Installation and Set-up
1-14
SIMATIC TI505/TI500 MODNIM User Manual
1.5 Switches and Indicator Lights
The
three switches located on the face of the module behind the access door
are Reset, Self T
est, and Local/Remote, and are described in the following
paragraphs.
The Reset button is a momentary-contact switch which initializes the
MODNIM and initiates the power
-up self test. When you press Reset, all the
indicators turn on for approximately 1 second. Then, all indicators except
TEST go off for about 5 seconds. During this time, the MODNIM runs a
series of diagnostic tests to verify that the hardware components of the
module are operating properly
. In addition, buffers and counters that
service the Modbus Diagnostic Functions are initialized.
If the tests have been successfully completed, only the NIM GOOD and the
PC GOOD (PC/NIM COMM GOOD) indicators will turn back on, while the
TEST indicator turns off. If, however
, the TEST indicator
remains on, run
the User Initiated Self-Test to determine the source of the error
.
NOTE:
Always press the Reset button after you change any of the
configuration dipswitches or address selection dipswitches. In addition, be
aware that when the MODNIM is reset, no communication can occur from
the host to the module for several seconds.
The T
est button initiates a series of diagnostic tests when it is held down for
3 seconds after a Reset operation. Before running the diagnostic tests,
disconnect all communications cables and install loopback connectors on the
RS-232-C communications ports. These tests are described in more detail in
Section 1.6.
When set to Remote, this two-position toggle switch enables the MODNIM
to perform write operations to PLC memory
. In the Local position, the
MODNIM cannot write to the PLC.
In either position, the MODNIM can monitor PLC memory and mode of
operation. After the MODNIM is set to Online state, local or remote status
is indicated as follows.
Local
mode is indicated by a
flashing
ONLINE indicator
.
Remote
mode is indicated by a
steady
ONLINE indicator
.
When set to Local mode, only the Read functions 1, 2, 3, 4, 7, 1
1, 12, and 17
plus diagnostics function 8 can be performed. All other functions (write
operations) will be rejected with Exception Code 01.
Switches and
Buttons
Reset Button
T
est Button
Local/Remote
Switch