OpenAir™ GCA Series Spring Return 160 lb-in Electronic Damper Actuator Technical Instructions
Document No. 155-173P25
November 5, 2012
Control Signal
Adjustment
GCA 163 and GCA164
The offset (start point) and span of the control signal can be adjusted. The offset,
Uo, can be adjusted between 0 to 5 Vdc. The span, ΔU, can be adjusted between
2 to 30 Vdc.
Ys Mechanical positioning range
(100% = angle of rotation 90°)
Yu Control signal
Uo Offset (start point)
ΔU Span
Uo = 0V, ΔU = 2V
The minimum working range for Ys = 100%
1. Uo = 5V, ΔU = 30V The maximum
working range for Ys = 100%
2. Uo = 0V, ΔU ≈ 10V Factory setting
Offset, Uo
2
4
0
1
3
5
Span, U
30
2
15
10
5
20
25
Control
Signals
Uo
U
EA0287R1
Setting for
10V span
0V offset
Figure 13. The Minimum and Maximum Control Signal Adjustment.
Example:
Open the actuator from 0% to 50% (45°) using a control signal of
Umin = 2V to Umax = 10V.
Calculating the value of ΔU:
V16
50
2)(10 x 100
% in rotation of angle Working
min) Umax (U %] [ 100
U =
−
=
=Δ
Siemens Industry, Inc. Page 9